Setting Guidelines; Time Synchronization; Application - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
the Main menu/Test/Function status/Function group/Function block descriptive name/LN
name/Outputs.
When the
control commands with a test bit are accepted.
When the
bit are accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the
function block. Only process-related outputs on function blocks related to primary
equipment are blocked. If there is an XCBR function block used, the outputs
and
When the
are accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the
function block. In addition, the function block can be blocked when their
This can be done if the function block has a block input.
The block status of a component is shown on the LHMI as the
Beh: Main menu/Test/Function status/Function group/Function block descriptive
as for
name/LN name/Outputs. If the
21.12.2

Setting guidelines

Remember always that there are two possible ways to place the IED in the
state. If, the IED is set to normal operation (
being in the test mode, the input signal IED_TEST on the TESTMODE function block is
activated in the configuration.
Forcing of binary input and output signals is only possible when the IED is in IED test mode.
21.13

Time synchronization

21.13.1

Application

Use time synchronization to achieve a common time base for the IEDs in a protection and
control system. This makes it possible to compare events and disturbance data between all
IEDs in the system. If a global common source (i.e. GPS) is used in different substations for the
time synchronization, also comparisons and analysis between recordings made at different
locations can be easily performed and a more accurate view of the actual sequence of events
can be obtained.
Time-tagging of internal events and disturbances are an excellent help when evaluating faults.
Without time synchronization, only the events within one IED can be compared with each
other. With time synchronization, events and disturbances within the whole network, can be
compared and evaluated.
In the IED, the internal time can be synchronized from the following sources:
BIN (Binary Minute Pulse)
DNP
GPS
IEC103
SNTP
IRIG-B
SPA
LON
PPS
Application manual
Beh of a function block is set to Test , the function block is not blocked and all
Beh of a function block is set to Test/blocked , all control commands with a test
EXC_Close are blocked.
Beh of a function block is set to Blocked , all control commands with a test bit
Blk output is not shown, the component cannot be blocked.
TestMode = Off ), but the functions are still shown
Basic IED functions
EXC_Open
Beh is blocked .
Blk output under the same path
TestMode = On "
Section 21
M15260-3 v7
IP1750-1 v1
M11345-3 v9
453