I/O Signal Wiring - Mitsubishi Electric MR-J5 Series User Manual

Ac servo system
Hide thumbs Also See for MR-J5 Series:
Table of Contents

Advertisement

Using options or peripheral equipment
■Regenerative option
• The lead wire between the P+ terminal and D terminal should not be connected.
• The wires of the regenerative option should be connected to the P+ terminal and C terminal.
• Twisted wires should be used for connecting the regenerative option to the servo amplifier.
Page 144 Connection of regenerative option
■Simple converter
• The wires of the simple converter should be connected to the P4 terminal and N- terminal.
Page 151 Configuration including peripheral equipment
■The power factor improving DC reactor should be connected between P3 and P4.
Page 173 Power factor improving DC reactor
Power factor
improving
DC reactor
*1
*1 Be sure to disconnect the wire between P3 and P4.

I/O signal wiring

• The I/O signals should be connected correctly. If the DO forced output mode is used, the pins of the CN3 connector can be
forcibly switched on/off. This mode is used to check the wiring. In this case, switch on the control circuit power supply only.
Refer to the following for details on I/O signal connection.
Page 28 I/O signal connection example
• A voltage exceeding 24 V DC should not be applied to the pins of the CN3 connector.
• The plate and DOCOM of the CN3 connector should not be shorted.
Servo amplifier
CN3
DOCOM
Plate