C2: S-Curve Characteristics - YASKAWA Z1000 CIMR-ZU*A Series Programming Manual

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

1.3 C: Tuning
(accel time from 0 Hz to C1-11)
C1-03 =
(accel time between C1-11 and E1-04)
C1-01 =
(decel time between E1-04 and C1-11)
C1-02 =
(decel time from C1-11 to 0 Hz)
C1-04 =
n
C1-11: Accel/Decel Time Switching Frequency
Sets the frequency at which the drive switches between accel/decel time settings.
a Frequency Level on page 51
No.
C1-11
Note:
Setting C1-11 to 0.0 disables this function.
n
C1-09: Fast Stop Time
Sets a special deceleration used when a select group of faults occur or when closing a digital input configured as H1-oo =
15 (N.O. input) or 17 (N.C. input). A momentary closure of the digital input will trigger the Fast Stop operation; it does not
have to be closed continuously.
The drive cannot be restarted after initiating a Fast Stop operation until after completing deceleration, clearing the Fast Stop
input, and cycling the Run command.
A digital output programmed for "During Fast Stop" (H2-oo = 4C) will be closed as long as Fast Stop is active.
No.
C1-09
NOTICE: Rapid deceleration can trigger an overvoltage fault. The drive output shuts off when faulted and the motor coasts. Set an
appropriate Fast Stop time to C1-09 to avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely.
u

C2: S-Curve Characteristics

Use S-curve characteristics to smooth acceleration and deceleration and minimize abrupt shock to the load. Set S-curve
characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop. Increase the value set to
C2-01 if the STo fault (Step Out Detection) occurs when starting a PM motor.
n
C2-01 and C2-02: S-Curve Characteristics
C2-01 and C2-02 set separate S-curves for each section of the acceleration or deceleration.
No.
C2-01
C2-02
Figure 1.21
illustrates S-curve application.
52
×
(E1-04)
C1-11
×
(E1-04)
(E1-04 - C1-11)
×
(E1-04)
(E1-04 - C1-11)
×
(E1-04)
C1-11
Figure 1.20 Accel/Decel Time Switching Frequency
for details.
Parameter Name
Accel/Decel Time Switching Frequency
Parameter Name
Fast Stop Time
Parameter Name
S-Curve Characteristic at Accel Start
S-Curve Characteristic at Accel End
Output Frequency
C1-11
Accel/Decel Time
Switch Frequency
C1-03
C1-01
setting
setting
When the output frequency
C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-03, -04)
Refer to Switching Accel/Decel Times by
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
C1-02
C1-04
setting
setting
Setting Range
0.0 to 240.0 Hz
Setting Range
0.1 to 6000.0 s
Setting Range
Determined by
0.00 to 10.00 s
Default
0.0 Hz
Default
10.0 s
Default
A1-02
0.20 s