Last Station Number Setting - Mitsubishi Melsec-L Series User Manual

Cc-link/lt master module
Hide thumbs Also See for Melsec-L Series:
Table of Contents

Advertisement

6.5

Last Station Number Setting

The last station number is set to perform data link up to the last remote station in connection with the network and not
to perform data link with unconnected stations.
This setting is optional but useful to optimize link scan time.
When 16-point mode is set, the number of occupied I/O points is set to 128 points, and the last remote
Ex.
station in connection with the network is numbered as "5"
By setting "5" as the last station number, the link scan time is optimized.
Remote
station
Data link range when the last station number is set to 5
(1) Setting procedure
Set the last station number using the intelligent function module switch setting of GX Works2.
Parameter
Remote
Remote
station
station
No.1
No.2
No.3
Data link range when the last station number is not set
[PLC Parameter]
CHAPTER 6 INSTALLATION AND WIRING
Remote
Remote
Remote
station
station
station
No.4
No.5
No.6
[I/O Assignment]
Select "DEC".
Not connected
Remote
Remote
station
station
No.7
No.8
button
49