Mitsubishi Melsec-L Series User Manual page 73

Cc-link/lt master module
Hide thumbs Also See for Melsec-L Series:
Table of Contents

Advertisement

(9) Detailed remote station information (buffer memory address: 32 to 95 (Un\G32
to 95))
Information on each remote station is stored.
Bit
b2 to b0
Number of I/O points
b3
b4
b5
Remote device station flag
b6
Start station flag
b7
Input filter setting
b8
Output clear/hold setting
b15 to b9
*1
For I/O modules, the number of input or output points is stored.
For the CL1XY2-DT1D5S, 1 point is stored.
Ex.
*2
b4 and b3 indicate the presence of the remote input signal and remote output signal of the connected remote station.
For a remote I/O station used for input and output, both b4 and b3 store 1. For the one used for input, b4 and b3
Ex.
store 1 and 0, respectively.
*3
For a module having two or more occupied stations, only the bit of the buffer memory area in the start station will turn on.
Name
*1
000: 1 pt. 001: 2 pts. 010: 4 pts. 011: 8 pts. 100: 16 pts.
0: No output
*2
Output flag
1: Data being output
0: No input
*2
Input flag
1: Data being input
0: Remote I/O station
1: Remote device station
0: Station other than the start station
*3
1: Start station
0: Standard input (No setting)
1: High-speed input
0: Clear (No setting)
1: Hold
Empty
APPENDICES
Description
A
71