• A remote station may occupy multiple station numbers depending on the point mode setting and the number
of I/O points of the remote station. When using a remote station having the number of I/O points of eight or
more, check that the station number of the remote station is not duplicated with that of the next station.
8-point remote stations are numbered as station numbers 1 and 2
Ex.
• Point mode setting: 8-point mode (8 points/station)
• Point mode setting: 4-point mode (4 points/station)
(6) Connecting a remote station for CC-Link to CC-Link/LT
A CC-Link remote station cannot be connected to the master module. Doing so may cause system malfunction.
(7) Connecting a remote station for CC-Link/LT to CC-Link
A CC-Link/LT remote station cannot be connected to the master station on CC-Link. Doing so may cause system
malfunction.
8-point remote
8-point remote
station
station
(1 station occupied)
(1 station occupied)
Station (1) (8 points)
Station (2) (8 points)
Station No. 1
Station No. 2
Station No. not duplicated
8-point remote
8-point remote
station
station
(2 stations occupied)
(2 stations occupied)
Station (1)
Station (2)
Station (2)
(4 points)
(4 points)
(4 points)
Station No. 1
Station No. 2
Station No. of station (2) duplicated
CHAPTER 5 SYSTEM CONFIGURATION
Station (3)
(4 points)