How to perform the ID Run

For this application, the Standard ID Run must be performed.
Uncouple the motor from the spool if possible. If the motor cannot be uncoupled from
the spool, ensure the spool is at core.
Note: DIIL must be made and
input made in order to perform the ID Run.

ID Run Procedure

Note: If parameter values (Group 10 to 98) are changed before the ID Run, check
that the new settings meet the following conditions:
20.01
20.02
20.03
20.04
22.02
70.06
• Ensure that the panel is in the local control mode (L displayed on the status row).
Press the LOC/REM key to switch between modes.
• Change the selection to STANDARD.
1 L ->1242.0 rpm
99 START-UP DATA
10 MOTOR ID RUN
[STANDARD]
• Press ENTER to verify selection. The following message will be displayed:
1 L ->1242.0 rpm
ACS 800 55 kW
**WARNING**
ID RUN SEL
• To start the ID Run, press the
Warning when the ID Run is
started
1 L -> 1242.0 rpm
ACS 800 55 kW
**WARNING**
MOTOR STARTS
16.01
MINIMUM SPEED < 0 rpm
MAXIMUM SPEED > 80% of motor rated speed
MAXIMUM CURRENT > 100% · I
MAXIMUM TORQUE > 50%
ACCEL TIME 1 < 1 s
CH2 M/F MODE - Set to "Not In Use"
O
O
Warning during the ID Run
I
1 L -> 1242.0 rpm
ACS 800 55 kW
**WARNING**
ID RUN
RUN ENABLE must be set to "Yes" or the digital
hd
key.
Warning after a successfully
completed ID Run
I
1 L -> 1242.0 rpm
ACS 800 55 kW
**WARNING**
ID DONE
7
I
Start-up