Warning messages generated by the drive

Warning
Cause
Drive IGBT temperature is excessive. Fault trip
ACS800 TEMP
limit is 100%.
(4210)
02.15 AW 1 bit 04
BACKUP USED
PC stored backup of drive parameters is
downloaded into use.
(FFA3)
BATT FAILURE
APBU branching unit memory backup battery
error caused by
(5581)
- incorrect APBU switch S3 setting
- too low battery voltage.
BC OVERHEAT
Brake chopper overload
(7114)
BR OVERHEAT
Brake resistor overload
(7112)
CALIBRA DONE
Calibration of output current transformers is
completed.
(FF37)
CALIBRA REQ
Calibration of output current transformers is
required. Displayed at start if drive is in scalar
(FF36)
control and scalar fly start feature is on.
COMM MODULE
Cyclical communication between drive and
master is lost.
(7510)
02.15 AW 1 bit 12
(programmable
Fault Function
30.18, 30.19)
Fault tracing
What to Do
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
Wait until download is completed.
With parallel connected inverters, enable
backup battery by setting actuator 6 of switch
S3 to ON.
Replace backup battery.
Stop drive. Let chopper cool down.
Check parameter settings of resistor overload
protection function (see parameter group
BRAKE
CHOPPER).
Check that braking cycle meets allowed limits.
Check that drive supply AC voltage is not
excessive.
Stop drive. Let resistor cool down.
Check parameter settings of resistor overload
protection function (see parameter group
BRAKE
CHOPPER).
Check that braking cycle meets allowed limits.
Continue normal operation.
Calibration starts automatically. Wait for a
while.
Check status of fieldbus communication. See
chapter
Fieldbus
control, or appropriate
fieldbus adapter manual.
Check parameter settings:
- group
51 FIELDBUS DATA
adapter)
- group
52 STANDARD MODBUS
Standard Modbus Link).
Check Fault Function parameters.
Check cable connections.
Check if master can communicate.
27
27
(for fieldbus
(for