ABB ACS800 Series Firmware Manual page 146

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

134
No.
Name/Value
98.06 AI/O EXT MODULE
NAIO
NO
RAIO-SLOT1
RAIO-SLOT2
RAIO-DDCS
98.09 DI DEBOUNCE FILT
0...1000 ms
Actual signals and parameters
Description
Activates the communication to an optional Analog I/O Extension
Module.
Note: Before setting the drive parameters, ensure the module
hardware settings are OK:
- The module node number is set to 5.
- The input signal type selections matches the actual signals (mA/V).
- The operation mode selection matches the applied input signals
(unipolar/bipolar).
Communication active. Module type: NAIO. Connection interface:
Fibre optic DDCS link.
Note: Module node number must be set to 5. For directions, see
Installation and Start-up Guide for NTAC-0x/NDIO-0x/NAIO-0x
Modules (Code: 3AFY58919730 [English]).
Communication inactive.
Communication active. Module type: RAIO. Connection interface:
Option slot 1 of the drive.
Communication active. Module type: RAIO. Connection interface:
Option slot 2 of the drive.
Communication active. Module type: RAIO. Connection interface:
Optional I/O module adapter (AIMA) that communicates with the drive
through a fibre optic DDCS link.
Note: Module node number must be set to 5. For directions, see
User's Manual for RAIO Module (Code: 3AFE64484567 [English]).
Digital input de-bounce filter. Prevents unwanted ON/OFF switching of
the digital inputs.
Setting range.
FbEq
1
2
3
4
5
1 = 1 ms