5 Troubleshooting
5-4
Troubleshooting with Emergency
Messages
EtherCAT Slave Units are able to report emergency messages to the EtherCAT master by using the
SDO communications if they detect errors.
5-4-1

Emergency Message Notification

When the power supply is turned ON, the EtherCAT Slave Unit always starts with the Notification set-
ting.
Emergency messages cannot be sent while there is an EtherCAT communications error.
Byte
Contents
Emergency error code
Refer to 5-4-2 Emergency Error Codes on page 5-16 for the meanings of the emergency messages.
5-4-2

Emergency Error Codes

The following table lists the emergency error codes that are used with EtherCAT Slave Units and the
meaning of each error.
Error
code
Error type
(hex)
5530
Memory access
error
6140
6120
Unit error
7030
5 - 16
0
1
2
Reserved
Error name
Description
Special Unit
An error occurred while
Memory Error
reading or writing the error
log.
All error log records cannot
be used during initialization
or registering an error log
record.
SII Unit Verifi-
An error occurred in the
cation Error
slave information stored in
SII when the power supply
was turned ON.
Special Unit
An error occurred in the
Error
EtherCAT Slave Unit.
ESC Error
An error occurred in the
ESC.
3
4
5
0000 hex
Notification to
EtherCAT
master
Yes
No
CJ-series EtherCAT Slave Units Operation Manual (W541)
6
7
Corrective action
Restart the EtherCAT
Slave Unit.
Replace the EtherCAT
Slave Unit if the error
recurs.
Restart the CPU Unit.
Replace the EtherCAT
Slave Unit if the error
recurs.
Replace the EtherCAT
Slave Unit if the same error
recurs when the Unit is
mounted to another CPU
Unit.