Cooling circuit
Cool only unit: Includes Schrader valves on the high, low
and liquid sides, high and low pressure switches, filter-dryer,
expansion valve (YLCA- 5 to 15), expansion valve and liquid
sight glass (YLCA 20 to 27), and service valves for isolating
the condensing unit (pump down) (YLCA 27).
Heat pump unit: Includes Schrader valves on the high and low
sides, high and low pressure switches, filter-dryer, two expan-
sion valves (YLHA PLUS 5 to 15), two expansion valves and
liquid sight glass (YLHA PLUS 20 to 27), service valves for
isolating the condensing unit (pump down) (YLHA PLUS 27),
liquid tank, four-way valve (energized in summer cycle) and
check valves (YLHA PLUS 20 to 27). The suction tubing is
coated with closed-cell elastomer.
Hydro kit
These units include a pack assembled with the components
of a hydro kit. This assembly is located within the unit frame
and does not increase the footprint of same. It includes the
following components: Centrifugal pump, expansion vessel
charged with nitrogen at 1.5 bar, relief valve set to 6 bar, flow
switch, air bleed valve and drain connection. Also includes
a mesh filter for the water circuit. This filter is supplied loose
for installation at the most convenient point.
Protecting grids
To protect the coils from possible impacts. Made of steel
rods and painted with oven baked polymerized white enamel
(RAL9001).

Accessories and options

Remote control unit
Wall-mounted remote control unit with keyboard for cool/heat
and ON/OFF functions. Includes power supply, alarm and
cool/heat LEDs. Maximum cable length: 50 m.
Remote terminal
For total access and control of the system by means of the
display and keys. Allows selecting cool, heat and off functions.
Can also modify operating parameters and monitor the sys-
tem. Can be installed at a maximum distance of 1040 m.
BMS connections
By means of a serial board, it is possible to connect the
system to a standard RS485 monitoring network.
Low ambient temperature kit (YLCA 5 to 15)
Includes a pressure transducer for controlling condensing
pressure at low ambient temperature (-18°C).
Standard on models YLCA 20 & 27, and YLHA PLUS 5-27.
High pressure fans
Buffer tank
With a backup heater installed.
Antivibratory supports
Whenever necessary to reduce to a maximum vibrations
and noise caused by the unit, you can use a set of caoutch
antivibratory supports, that should be installed between the
supporting chassis of the unit and the base or floor on which
same should be set. This base should be solid and dimen-
sioned in accordance with the weight to be supported. To
fasten the supports to the base of the chassis, 8/10Ma screws
are used. The antivibratory supports accessory includes 4
parts. These supports should be distributed amongst and
fastened in the drilled holes in the base, the location of which
is detailed in the General Dimensions section.
YLCA/YLHA PLUS 5 ÷ 15
30
15
90
YLCA/YLHA PLUS 20 ÷ 27
45
15
160
8MA
65
50
10MA
130
7