Tray Heater - York YLCA Series Technical Information

R-410a
Hide thumbs Also See for YLCA Series:
Table of Contents

Advertisement

Tray heater YLHA PLUS 5-15
This flexible cable heater can be used in cold climates to
avoid the forming of ice and the subsequent obstruction at
the tray drain of the heat pumps.
This accessory includes:
1 Flexible cable heater with a thermostat.
2 m, of 50 mm, self-adhesive aluminium tape.
Heater characteristics
Current: 230.1.50
Power: 80 W
Total length: 3 000 mm
Active heater length: 2 000 mm (contact with the coil)
Cold limit: 1 000 mm (open-air cable and connecting strip
connection)
Heater activation temperature: Indoor ambient 4° C.
THERMOSTAT
ACTIVE HEATER
2000
66
SELF-ADHESIVE
ALUMINIUM TAPE
COLD LIMIT
1000
3000
N4
Installation
N1- With the power supply turned off. remove the front panel
and the compressor chamber corner piece.
N2 - Fasten the end with the thermostat to the separating
panel of the fan chamber, at the indicated level. Use the
3.5 mm dia.
To fasten said end, us the section of self-ashesive alu-
minium tape installed.
N3- Locate the cable heater over the tray, at the indicated
elevation.
N4 - Pass the cable heater to the compressor chamber
through the rectangular hole at the base of the separat-
ing panel. Make sure the cable heater reaches the tray
drain.
N5 - Fasten the cable heater to the tray with the self-adhesive
aluminium tape supplied. Avoid covering the tray drain.
N6 - Connect the two terminal cables of the heater to termi-
nals L1 and N (230.1.50) of the connecting strip.
N6
N2
N5
30
N3