Module
AI 4x15Bit [EEx ib]
You cannot use the module in redundant operation for applications in hazardous areas.
It is not suitable for indirect current measurement.
Use in direct current measurement
Suitable Zener diode 6.2 V, for example BZX85C6v2
Load capability of 4-wire transmitters: RB > 325 ohms
determined for worst case: 1 input + 1 Zener diode at an S7 overload value of 24 mA to RB = (RE * I
Input voltage for 2-wire transmitters: Ue-2Dr < 8 V
calculated for worst case: 1 input + 1 Zener diode at an S7 overload value of 24 mA to Ue-2Dr = RE * I
Note: You can only connect 2-wire transmitters with a 24 V external supply or 4-wire transmitters. The internal power sup-
ply for transmitters cannot be used in the circuit because it outputs only 13 V, which means in the worst case it would sup-
ply only 5 V to the transmitter.
AI 8x0/4...20mA HART
A firmware update is not possible in redundant operation.
Online calibration is not possible in redundant operation.
ET 200M Distributed I/O Device; HART Analog Modules
See Manual
AI6x0/4...20mA HART
F module in standard mode
AI 6x13Bit
F module in standard mode
Redundant AO dual-channel
AO4x12 Bit
AO8x12 Bit
AO4x0/4...20 mA [EEx ib]
You cannot use the module in redundant operation for applications in hazardous areas.
AO 8x0/4...20mA HART
A firmware update is not possible in redundant operation.
Online calibration is not possible in redundant operation.
ET 200M Distributed I/O Device; HART Analog Modules
See Manual
Note
You need to install the F-ConfigurationPack for F modules.
The F ConfigurationPack can be downloaded free of charge from the Internet.
You can find it on the Customer Support site at Download of F Configuration Pack
(http://support.automation.siemens.com/WW/view/en/15208817)
Using digital input modules as redundant I/O
The following parameters were set to configure digital input modules for redundant
operation:
● Discrepancy time (maximum permitted time in which the redundant input signals may
differ). The specified discrepancy time must be a multiple of the update time of the
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
6.7 Connection of two-channel I/O to the PROFIBUS DP interface
manual
I/O configuration variants
Article No.
6ES7331-7RD00-0AB0
max +
max
6ES7 331-7TF01-0AB0
6ES7336-4GE00-0AB0
6ES7 336-1HE00-0AB0
6ES7332-5HD01-0AB0
6ES7332-5HF00-0AB0
6ES7332-5RD00-0AB0
6ES7 332-8TF01-0AB0
U
)/I
z max
max
+ U
z max
87