Synchronization modules
14.1 Synchronization modules for the CPU 410.
5. Repeat steps 1 to 4 for the second synchronization module.
6. Repeat the process for the second fault-tolerant CPU.
Connect the IF1 interface of the first CPU with the IF1 interface of the second CPU and
the IF2 interface of the first CPU with the IF2 interface of the second CPU.
Note
Wiring synchronization modules crosswise
If you wire synchronization modules crosswise, i.e. the IF1 interface of the first CPU with
the IF2 interface of the second CPU and vice versa, the two CPUs take over the master
role and the system will now function properly. The LEDs IFM 1 and IFM 2 are lit on both
CPUs.
Make sure that you connect the IF1 interface of the first CPU with the IF1 interface of the
second CPU and the IF2 interface of the first CPU with the IF2 interface of the second
CPU.
Removing the synchronization module
1. Slightly press the release of the fiber-optic cable and remove it from the synchronization
module.
2. Fold the clip of the synchronization module to the front and remove the synchronization
module from the fault-tolerant CPU interface.
3. Place the dummy plug on the synchronization module.
4. Repeat this procedure for all interfaces and both fault-tolerant CPUs.
Technical specifications
Technical specifications
Maximum distance between the
CPUs
Supply voltage
Current consumption
Power loss
Wavelength of the optical
transceivers
Maximal permitted attenuation of the
fiber-optic cable
Maximum permitted difference in
cable lengths
Dimensions W x H x D (mm)
Weight
242
6ES7 960–1AA06–0XA0
10 m
3.3 V, supplied by the CPU
220 mA
0.77 W
850 nm
7.5 dB
9 m
13 x 14 x 58
0.014 kg
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
6ES7 960–1AB06–0XA0
10 km
3.3 V, supplied by the CPU
240 mA
0.83 W
1310 nm
9.5 dB
50 m
13 x 14 x 58
0.014 kg