Flush-Mounted In Metal; Minimum Spacing - Siemens SIMATIC Ident System Manual

Hide thumbs Also See for SIMATIC Ident:
Table of Contents

Advertisement

6.6.4

Flush-mounted in metal

a
Figure 6-27
6.6.5

Minimum spacing

Note
Extension of the data transmission time if distance values are undershot
If the distance values specified in the tables are undershot, it is possible that the inductive
fields will be affected. In this case, the data transmission time can increase unpredictably or
a command is aborted with an error.
For this reason, please observe the values in the tables.
Minimum distances from transponder to transponder (without multitag mode)
RF290R
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
= 150 mm
Metal-free area for ANT D5
MDS D100 / MDS D126 / MDS D139 /
MDS D165 / MDS D200 / MDS D261 /
MDS D339 / MDS D400 / MDS D426 /
MDS D526
≥ 1 m
MDS D124 / MDS D160 / MDS D324 /
MDS D424 / MDS D428 / MDS D460 /
MDS D524 / MDS D528 / MDS D560
≥ 0.8 m
Antennas
6.6 ANT D5
171