Modifications to the System while in Operation
10.3.6

PCS7, Step VI: Transition to the Redundant System Mode

Initial situation
The fault-tolerant system works with the new hardware configuration in Solo mode.
Procedure
1.
In SIMATIC Manager select a CPU of the fault-tolerant system and select the
menu command PLC > Operating Mode.
2.
In the Operating Mode dialog box select the standby CPU and click the
Restart (warm restart) button.
Result
Standby CPU links up again and is updated. The fault-tolerant system works with
the new hardware configuration in the Redundant system mode.
Reaction of the I/O
Type of I/O
One-way I/O of standby
I/O modules to be
Are no longer addressed by the CPU.
1)
removed
Driver blocks are no longer present.
I/O modules that
Are re-parameterized
continue to be
and updated by the CPU.
present
DP stations to be
as for I/O modules to be removed (see above)
removed:
1) no longer contained in the hardware configuration, but still plugged in
2) Central modules are first reset in addition. Output modules briefly output 0 during this time (instead of the
substitute or holding values configured).
Reaction if monitoring times are exceeded
If one of the monitored times exceeds the maximum value configured the update is
interrupted. The fault-tolerant system remains in Solo mode with the previous
master CPU and in certain conditions attempts to perform the link-up and update
later. For more details refer to Section 5.3.
10-22
One-way I/O of master
CPU
2)
Continue to work without interruption.
S7-400H Programmable Controller Fault-Tolerant Systems