Pcs7, Step V: Switch To Cpu With Modified Configuration - Siemens SIMATIC S7-400H Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Modifications to the System while in Operation
10.3.5

PCS7, Step V: Switch to CPU with modified configuration

Initial situation
The modified hardware configuration is loaded into the standby CPU.
Procedure
1.
In SIMATIC Manager select a CPU of the fault-tolerant system and select the
menu command PLC > Operating Mode.
2.
In the Operating Mode dialog box click the Switch to button.
3.
In the Switch to dialog box select the option with modified configuration
and click the Switch button.
4.
Confirm the check question that follows with OK.
Result
The standby CPU connects, is updated (see Chapter 5) and becomes the master.
The former master CPU switches to STOP mode, the fault-tolerant system works
with the new hardware configuration in Solo mode.
Behavior of the I/O
Type of I/O
One-way I/O of previous
I/O modules to be
Are no longer addressed by the CPU.
1)
removed
Driver blocks are no longer present.
I/O modules that
Are no longer addressed
continue to be
by the CPU.
present
Output modules output the
configured substitute or
holding values.
DP stations to be
as for I/O modules to be removed (see above)
removed:
1) no longer contained in the hardware configuration, but still plugged in
2) Central modules are reset first in addition. Output modules briefly output 0 during this time (instead of the
configured substitute or holding values).
10-20
One-way I/O of new
master CPU
Are re-parameterized
and updated by the CPU.
S7-400H Programmable Controller Fault-Tolerant Systems
master CPU
2)
Continue to work without
interruption.
Switched I/O
A5E00068197-04