10.2.5

PCS7, Step 5: Switch to CPU with modified configuration

Initial situation
The modified hardware configuration is loaded into the standby CPU.
Procedure
1.
In SIMATIC Manager select a CPU of the fault-tolerant system and select the
menu command PLC > Operating Mode.
2.
In the Operating Mode dialog box click the Switch to button.
3.
In the Switch to dialog box select the option with modified configuration
and click the Switch button.
4.
Confirm the check question that follows with OK.
Result
The standby CPU connects, is updated (see Chapter 5) and becomes the master.
The former master CPU switches to STOP mode, the fault-tolerant system works
with the new hardware configuration in Solo mode.
Behavior of the I/O
Type of I/O
One-way I/O of previous
Added I/O modules Are not addressed by the
CPU.
I/O modules that
Are no longer addressed
continue to be
by the CPU.
present
Output modules output the
configured substitute or
holding values.
Added DP stations
Are not addressed by the
CPU.
1) Central modules are reset first in addition. Output modules briefly output 0 during this time (instead of the
configured substitute or holding values).
S7-400H Programmable Controller Fault-Tolerant Systems
A5E00068197-04
Modifications to the System while in Operation
One-way I/O of new
master CPU
Are parameterized and updated by the CPU.
Driver blocks are not yet present. Any process or
diagnostic interrupts occurring will be recognized but
not reported.
Are re-parameterized
and updated by the CPU.
as for added I/O modules (see above)
master CPU
1)
Continue to work without
interruption.
Switched I/O
10-11