Modifications to the System while in Operation
10.3

Removing Components in PCS7

Initial situation
You have ensured that the CPU parameters (e.g. the monitoring times) suit the
planned new program. If necessary you must first change the CPU parameters
accordingly (see Section 10.6).
The modules to be removed and the associated sensors and actuators are no
longer of any significance for the process to be controlled. The fault-tolerant
system is working in the Redundant system mode.
Procedure
In order to remove hardware components from a fault-tolerant system under PCS7
the steps listed below are to be performed. Details of each step are listed in a
subsection.
Step
I
Offline Modification of the Hardware Configuration
II
Changing and Loading User Program
III
Stopping the Standby CPU
IV
Loading new Hardware Configuration in the Standby CPU
V
Switch to CPU with modified configuration
VI
Transition to the Redundant System Mode
VII
Modification of Hardware
10-16
What Has To Be Done?
S7-400H Programmable Controller Fault-Tolerant Systems
Refer to Section
10.3.1
10.3.2
10.3.3
10.3.4
10.3.5
10.3.6
10.3.7
A5E00068197-04