Step 7, Step 2: Offline Modification Of The Hardware Configuration - Siemens SIMATIC S7-400H Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Modifications to the System while in Operation
10.4.2
STEP 7, Step 2: Offline Modification of the Hardware
Configuration
Initial situation
The fault-tolerant system is working in the Redundant system mode. The modules
added will not yet be addressed.
Procedure
1.
Perform all the modifications to the hardware configuration relating to the
added hardware offline.
2.
Compile the new hardware configuration, but do not load it into the PLC yet.
Result
The modified hardware configuration is in the PG. The PLC continues to work with
the old configuration in the Redundant system mode.
Configuring connections
Connections from or to newly added CPs must be configured for both connection
partners after modification of the hardware configuration is complete.
10.4.3
STEP 7, Step 3: Expanding and Loading Organization Blocks
Initial situation
The fault-tolerant system is working in the Redundant system mode.
Procedure
1.
Make sure that the interrupt OBs 4x, 82, 83, 85, 86 and 122 react in the
desired way to interrupts from the newly added components.
2.
Load the modified OBs and the program segments affected by these into the
PLC.
Result
The fault-tolerant system is working in the Redundant system mode.
10-26
S7-400H Programmable Controller Fault-Tolerant Systems
A5E00068197-04