4. Set Up and Calibration Procedures -
Lower Display
Prompt
MANRST
LD CAL
LD CFG
RESTRT
* Temperature units are displayed in degrees C or F, and are set by the UNITS parameter. See SET
DISPLA set up group.
† Note that the upper display contains the parameter name and the lower display contains the value.
This is to allow for the display of hours: minutes: seconds.
54
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Upper Display
Selections or
Range of Setting
MAINTENANCE STATISTIC RESET—Allows reset of the
following maintenance statistics:
NONE
None—No reset of maintenance statisitics
STAL
Stall—Resets accumulated stall time to zero.
STRT
Motor Starts—Resets accumulated motor start counts to
zero.
REGNn
Motor Starts in the Region—Resets to zero the
n = 0 to 9
accumulated motor starts for n
TEMP
Temperature Statistics—Resets the high / low temperature
limit statistics to zero.
TDEG
Total Degrees—Resets the total degrees of motor travel to
zero.
RELn
Relay Counts—Resets accumulated relay cycle counts to
n = 1, 2, 3 or 4
zero for the relay option number displayed.
ALL
All—Resets all maintenance statistics to zero.
SYST
System Restart--Enables the system restart function
NONE
RESTORE CALIBRATION TYPE—Allows you to restore a
[default]
calbration value to its factory calibration.
INP
Input—Restores input calibration to the factory calibration.
MTR
Motor—Restores motor calibration to the factory calibration.
COUT
Output—Restores actuator output calibration to the factory
calibration. For 4-20 mA output only; all other CUROUT
selections require output calibration.
ALL
All—Restores input, motor and output calibration to the
factory calibrations.
POS
Position Sensor—Restores position sensor calibration to
the factory calibration.
NOTE: Allows a position sensor field calibration to be stored
as a factory calibration. This is to be used after replacement
of the sensor in the field. See "Calibrate POS Output".
DIS
RESTORE DEFAULT FACTORY CONFIGURATION---
Allows you to restore the factory default configuration values.
ENAB
DIS --- Restore disabled.
ENAB --- Restore enabled.
DIS
SYSTEM RESTART --- Allows you to force the system to go
thru a restart.
ENAB
DIS --- Restart disabled.
ENAB --- Restart enabled.
Note: The MANRST function must be set to SYST.
Parameter Definition
th
10% of motor span.
Revision 5
7/07