Smart actuator
Table of Contents

Advertisement

4. Set Up and Calibration Procedures - Relays Set Up Group
Relay Type – Deviation, continued
Motor
Position
Relay Type – Upper Limit Travel with Hysteresis
Selecting relay type ULim will cause the relay to energize when the motor position exceeds the upper limit
trip point, and can be set up as follows. Note that relay hysteresis parameter (RLY1HY) value is set to 10,
which is 10% of range. This means that when the relay is energized, due to the motor position exceeding
the upper limit value, the relay will not de-energize until the motor moves to 10% below the trip point.
Motor
Position
Motor
Position
42
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
0%
Closed
Set Up Group
SET RELAY2
0%
Normally Open
0%
Normally Open
Input
50%
-10%
+10%
Open
RELAY n
Normally Open
Parameter
RTYP21
R21VAL
R21HL
RTYP22
RLY2HY
60%
70%
Open
RELAY n
60%
70%
Open
RELAY n
100%
Closed
Value
ULim
70.0
HI
NONE
10.0
100%
Closed
100%
Closed
Revision 5
7/07