Input Signals
Input Impedance
Input
Characterization
Sensitivity
Hysteresis
Deadband
Repeatability
Voltage/ Supply
Stability
Temperature
Coefficient
Zero Suppression
Input Filters
Solid State Motor
Control
Fail-safe Operation
Feedback Ssignals
Slidewire Emulation
Digital Input
Power Isolation
Load Requirement
(4-20)
Diagnostics
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
7/07
Specifications - Actuator with Digital Electronics
Electrical
Analog: 0/4 to 20 mA
(With supplied shunt resistor for current range: 250 ohms ±0.1 %
Part Number: 070756)
0/1 to 5 Vdc
0 to 10 Vdc
Digital:
Modbus RTU RS485 (Remote setpoint)
Input
0/4 to 20 mA
1 to 5 Vdc
Provides characterization of the input signal.
Selections are Linear, Square Root or Custom – Equal %, Quick Opening, User
Defined.
0.2% to 5% of 90° span, proportional to deadband
Less than 0.4% of full scale.
0.2% to 5.0% of 90° span, adjustable. Shipped at 0.5% span.
0.2% of 90° span
0.25% of span with +10/–15% voltage change
Less than ±0.030% of span per degree C for 0 °C to 50 °C
Less than ±0.05% of span per degree C for –30 °C to 75 °C
90 % of span
Selectable spike and low pass filters.
Two triac switches for clockwise or counterclockwise motor operation.
If input signal exceeds configured input range. Selectable and adjustable.
0 to 20 mA, or 4 to 20 mA
0 to 5 Vdc, or 1 to 5 Vdc with 250 ohm resistor ± 0.1 %
0 to 16 Vdc with 800 ohm resistor ± 0.1 %
Provides output voltage ratiometric to shaft position and potentiometric to supply
voltage (1-18 Vdc) without a slidewire. Emulates a 100 to 1000 ohm slidewire. 10 mA
output maximum
Contact closure: 5 Vdc provided by actuator.
Input and output signals are isolated from power.
Current Out, - 0 to 1000 Ω
Self-test diagnostics of RAM, SEE memory, Configuration and Calibration at power up.
Operation statistics recorded for predictive maintenance. See Maintenance Set Up
Group.
2. Specifications - Technical and Operating Specifications
Input Impedance
250 ohms
10 M ohms