Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 86

Single package rooftop units with systemvu controls version 2.x and puron r-410a refrigerant
Table of Contents

Advertisement

Display Text
NEW HARDWARE (cont)
OACFM SENS CHANNEL
FIRE SHUTDOWN SW
FILTER SW CHANNEL
REMOTE OCC CHAN
REM.SHUTDOWN CHAN
COFS CHANNEL
GEN STATUS CHAN
ENTHALPY SW CHAN
SIOB1 INSTALLED
NETWORK SETTINGS
BAS PROTOCOL
NETWORK TIMEOUT
CCN
BUS NUMBER
CCN ELEMENT #
CCN BAUDRATE
BROADCAST ACK?
BROADCAST SCHEDL?
BROADCAST TIME?
BROADCAST OAT?
BROADCAST OARH?
BROADCAST OAQ?
BROADCAST IAQ?
LOCATION
REFERENCE NUMBER
BACNET
MAC ADDRESS
BACNET BAUDRATE
AUTO ID SCHEME
BACNET AUTO ID
BACNET ID
LINKAGE SETTINGS
APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
Expanded Text
Quick Menu for New Hardware
OACFM Assigned Channel
Fire Shutdown Switch
Filter Status Sw Channel
Remote Occupancy Channel
Remote Shutdown Channel
COFS Assigned Channel
General Status Channel
Enthalpy Sw Channel
SIOB 1 Enabled
Building Network Configurations Menu
BAS Protocol Select
Network Input Timeout
CCN Network Configuration Menu
CCN Bus Number
CCN Element Number
CCN Baud Rate
CCN Broadcast Ack'er
Global Schedule Broadcst
CCN Time Broadcast
Broadcast OAT On Network
Broadcast OARH On Netwrk
Broadcast OAQ On Network
Broadcast IAQ On Network
Device Location
Reference number
BACnet network configuration menu
BACnet Device Macaddress
BACnet BMS baud rate
ALC Auto Id Scheme
BACnet ID Auto ID
BACnet ID Number
LINKAGE SETTINGS MENU
Range
Units
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB Ai10
0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
Yes/No
0=NONE,
x
1=CCN,
2=BACNET
0 to 600
min
0 to 239
1 to 239
0=9600,
1=19200,
2=38400
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
text string
text string
1 to 127
0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
Yes/No
Yes/No
0 to 4194302
86
Default
Point
0=None
OCFMCHAN
2: no FIOP
FIRE_CFG
0: FIOP
0=None
FILTCHAN
0=None
RMOCCHAN
0=None
ROFFCHAN
0=None
COFSCHAN
0=None
GEN_CHAN
0=None
ENTHCHAN
No for all except
SIOB1_EN
Humidimizer units
0=NONE
BMS_CFG
30
NETINTO
0
CCNBUS
1
CCNADD
2=38400
BAUDENUM
No
CCNBCACK
No
CCN_GSBC
No
CCNBC
No
OATBC
No
OARHBC
No
OAQBC
No
IAQBC
<blank>
DEV_LOC
<blank>
REF_NUM
01
BAC_MAC
4=76800
BAC_BAUD
Yes
AUID
Yes
BAC_AUID
1610101
BAC_ID