Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 141

Single package rooftop units with systemvu controls version 2.x and puron r-410a refrigerant
Table of Contents

Advertisement

APPENDIX D: SystemVut Controller CCN Tables
Table Name
Display Name
SET_PNT
Occupied Cool Setpoint
Occupied Heat Setpoint
Unoccupied Cool Setpoint
Unoccupied Heat Setpoint
Heat--- Cool Setpoint Gap
SPT Offset Range (+/--- )
Occupied SPRH Setpoint
Unoccupied SPRH Setpoint
Table Name
Display Name
CTLRID
Device Name:
Description:
Location:
Software Part Number:
Model Number:
Serial Number:
Reference Number:
Setpoint Table
Range
Units
55 to 80
° F
55 to 80
° F
65 to 95
° F
40 to 80
° F
2 to 10
^F
0 to 5
° F
0 to 100
%
0 to 100
%
Control ID Table
Range
Units
48_50LC_
text string
text string
CESR131651---XX---XX
2 to 10
0 to 5
0 to 5
141
Point Name
Default
OCSP
78
OHSP
68
UCSP
85
UHSP
60
HCSP_GAP
5
SPTO_RNG
5
SPRH_OSP
55
SPRH_USP
55
Point Name
Default

Hide quick links:

Advertisement

Table of Contents
loading