Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 67

Single package rooftop units with systemvu controls version 2.x and puron r-410a refrigerant
Table of Contents

Advertisement

Table 38 – LC 07- -26 VFD Status Parameters Available Through SystemVut Controller
Parameter Group
Running Hours
Operating Data
kWh Counter
Reference [%]
Status Word
General Status
Main Actual Value [%]
Power [kW]
Power [hp]
Motor Voltage
Motor Status
Frequency
Motor current
DC Link Voltage
Drive Status
Heatsink Temp.
Diagnostic Readouts
Alarm Word
NOTE: Table 38 lists the status information the VFD sends to the SystemVu controls. This table is updated at every scan the controls perform of the LEN.
This occurs approximately once every second.
Table 39 – LC 07- -26 VFD Motor Default Configurations - - Vertical Airflow Units
EQUIPMENT MODEL NUMBER (EQ_MOD)
Position 1,2
Position 7,8
48
07
48
07
48
07
48
07
48
07
48
07
48
07
48
07
48
07
48
08
48
08
48
08
48
08
48
08
48
08
48
08
48
08
48
08
48
08
48
08
48
08
48
09
48
09
48
09
48
09
48
09
48
09
48
09
48
09
48
09
48
09
48
09
48
09
48
12
48
12
48
12
48
12
48
12
48
12
48
12
48
12
48
12
Parameter Title
Danfoss Parameter
15--- 01
15--- 02
16--- 02
16--- 03
16--- 05
16--- 10
16--- 11
16--- 12
16--- 13
16--- 14
16--- 30
16--- 34
16--- 90
Position 10
Position 12
1
5
1
6
1
1
2
5
2
6
2
1
3
5
3
6
3
1
1
5
1
6
1
1
2
5
2
6
2
1
3
5
3
6
3
1
4
5
4
6
4
1
1
5
1
6
1
1
2
5
2
6
2
1
3
5
3
6
3
1
4
5
4
6
4
1
1
5
1
6
1
1
2
5
2
6
2
1
3
5
3
6
3
1
Units
SystemVu Point
h
RUNHOURS
kWh
KWHCNTR
%
REFSPEED
STATUSWD
%
kW
OUTPWRKW
hp
OUTPWRHP
V
OUTMVOLT
Hz
OUTMFREQ
A
OUTMCUR
V
DCLNVOLT
° C
ALMERRC
Nominal
Motor Voltage
Horse Power
MOTPWRHP
MOTVOLT
1.7
230
1.7
460
1.7
575
1.7
230
1.7
460
1.7
575
2.9
230
2.9
460
2.9
575
1.7
230
1.7
460
1.7
575
2.4
230
2.4
460
2.4
575
3.7
230
3.7
460
3.7
575
5.0
230
5.0
460
5.0
575
1.7
230
1.7
460
1.7
575
2.4
230
2.4
460
2.4
575
3.7
230
3.7
460
3.7
575
5.0
230
5.0
460
5.0
575
2.4
230
2.4
460
2.4
575
3.7
230
3.7
460
3.7
575
5.0
230
5.0
460
5.0
575
67
SystemVu Display Item
IDF VFD RUN HOURS
IDF VFD KW HOURS
VFD REF SPEED
VFD STATUS WORD
MAV
IDF VFD FEEDBACK
VFD OUTPUT KW
VFD OUTPUT HP
VFD OUTPUT VOLTS
VFD OUTPUT FREQ
VFD OUTPUT AMPS
IDF VFD DC VOLTS
HTSINKT
IDF VFD HSNK TEMP
IDF VFD ALM WORD
Motor Current
Motor Nominal
(Must--- Hold
Speed
Amps)
MOTCUR
MOTNOMSP
5.8
1695
2.9
1690
3.1
1690
5.8
1695
2.9
1690
3.1
1690
9.2
1735
4.2
1735
4.9
1710
5.8
1695
2.9
1690
3.1
1690
7.9
1680
3.6
1680
3.8
1680
11.7
1750
5.4
1750
4.9
1710
13.6
1745
6.8
1745
6
1745
5.8
1695
2.9
1690
3.1
1690
7.9
1680
3.6
1680
3.8
1680
11.7
1750
5.4
1750
4.9
1710
13.6
1745
6.8
1745
6
1745
7.9
1680
3.6
1680
3.8
1680
11.7
1750
5.4
1750
4.9
1710
13.6
1745
6.8
1745
6
1745
VFD Max Amps
VFD1MAXA
5.8
2.9
3.1
5.8
2.9
3.1
9.2
4.2
4.9
5.8
2.9
3.1
7.9
3.6
3.8
11.7
5.4
4.9
13.6
6.8
6.0
5.8
2.9
3.1
7.9
3.6
3.8
11.7
5.4
4.9
13.6
6.8
6.0
7.9
3.6
3.8
11.7
5.4
4.9
13.6
6.8
6.0