ITEM
OPERATING MODES
MODE
Operating Mode
SUBM
Operating Sub--- Mode
S.DMD
System Demand
LINK
Linkage Active
EFF.C
Cool Setpoint In Effect
EFF.H
Heat Setpoint In Effect
T.EFF
Effective Demand Temp
RH.OS
Occupied SPRH Setpoint
RH.US
Unoccupied SPRH Setpoint
CLTG
Cool Mode Select T.guard
HTTG
Heat Mode Select T.guard
DMD.C
Space Cooling Demand
TRD.C
Cooling Demand Trend
DMD.H
Heating Space Demand
TRD.H
Heat Space Demand Trend
DMD.S
CDLO
Cool Demand Limiting
HDLO
Heat Demand Limiting
CDML
Cool demand Limit Level
HDML
Heat demand Limit Level
CL.DO
Cool Demand limit offset
HT.DO
Heat Demand Limit offset
ITEM
ALARMS
CURR
alarm#
(repeat up to 25 times)
HIST
alarm#
(repeat up to 50 times)
R.CUR
R.HIS
ARxx
(repeat up to 20 times)
APPENDIX C: Navigatort Display
MODE - - OPERATING MODES
EXPANSION
see Appendix B
see Appendix B
see Appendix B
Yes/No
xx.x
xx.x
xxx.x
0 to 100
0 to 100
xxx
xxx
xx.x
xx.x
xx.x
xx.x
Off/On
Off/On
0 to 3
0 to 3
xx.x
xx.x
MODE - - ALARMS
EXPANSION
Curr Active Alarm Menu
text string
History Menu
alarm# --- mm/dd/yy---hh.mm--- text string
Reset All Current Alarms
Alarm Reset History Menu
mm/dd/yy, hh:mm:ss
RANGE
UNIT
WRITE STATUS
Yes
° F
° F
° F
%
%
sec
sec
° F
^F/min
° F
^F/min
° F
WRITE
RANGE
STATUS
ALARM01C --- ALARM25C
ALHIS001 --- ALHIS050
Yes/No
Yes
ALRESET
ALMRES00 --- ALMRES19
116
POINT
MODETEXT
SUBMTEXT
SYS_DMDT
LNK_ACT
CSP_EFF
HSP_EFF
TEMP_EFF
SPRH_OSP
SPRH_USP
COOLMSTG
HEATMSTG
COOL_DMD
CLDTREND
HEAT_DMD
HTDTREND
CDMLMOFF
HDMLMOFF
CDMDLLEV
HDMDLLEV
COOLDLMO
HEATDLMO
POINT

Hide quick links: