Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 107

Single package rooftop units with systemvu controls version 2.x and puron r-410a refrigerant
Table of Contents

Advertisement

ITEM
CONFIGURATION
GEN
General Unit Config Menu
S.DLY
Unit Startup Delay
U.CTL
Unit Control Type
T.CTL
Thermostat Hardware Type
ADST
Tstat Adaptive Staging
FT.TM
Change Filter Timer
T.TO
Test inactivity time out
CCH.T
CCH Max Temperature
STD.P
Std Barometric Pressure
L.INC
Linkage Stage inc. time
MX.SA
Unit's Maximum SAT
AC.SL
Auto Clr SAT Limit Fault
ATCS
Adaptive Temp Comp Start
TCS.U
User TCS Start bias time
IOB.E
SIOB 1 Enabled
DIS
DI Config Menu
FS.SW
Fire Shutdown Switch
FIL.C
Filter Status Sw Channel
HUM.S
HumidistatStatus Channel
HM.SW
Humidistat Switch Type
FIL.S
Filter Status Swith Type
RO.C
Remote Occupancy Channel
RO.SW
Remote Occupancy Sw Type
RS.C
Remote Shutdown Channel
RS.SW
Remote Shutdown Sw Type
RS.AT
Remote Shutdown ALM Type
COS.C
COFS Assigned Channel
CO.SW
COFS Switch Type
GEN.C
General Status Channel
APPENDIX C: Navigatort Display
MODE - - CONFIGURATIONS
EXPANSION
10 to 600
0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
Yes/No
0 to 9999
0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours,
5=8 hours,
6=12 hours
40 to 90
13 to 35
60 to 600
130 to 210
Yes/No
Enable/Disable
0 to 180
Yes/No
0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN,
1=NORM CLSD
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
0=NORM OPEN,
1=NORM CLSD
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
0=NORM OPEN,
1=NORM CLSD
0=Normal,
1=Emergency
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
0=NORM OPEN,
1=NORM CLSD
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
RANGE
UNIT
sec
30
0=TSTAT
2=CONV 3C2H
Yes
hours
600
4=4 hours
° F
65
in.Hg
29.92
sec
180
° F
200
No
Yes
min
0
2: no FIOP
0: FIOP
0=None
0=None
0=NORM OPEN
0=NORM OPEN
0=None
0=NORM OPEN
0=None
0=NORM OPEN
0=Normal
0=None
1=NORM CLSD
0=None
107
DEFAULT
POINT
STARTDLY
CTRLTYPE
STATTYPE
ADPTSTAT
FILTLIFE
TEST_ITO
CCHMAXT
STD_BARP
LSTAGINC
UMAX_SAT
SATLACLR
TCS_CFG
TCSUBIAS
SIOB1_EN
FIRE_CFG
FILTCHAN
HUMDCHAN
HUMD_CFG
FILT_CFG
RMOCCHAN
RMOC_CFG
ROFFCHAN
ROFF_CFG
ROFFTYPE
COFSCHAN
COFS_CFG
GEN_CHAN

Hide quick links: