Endress+Hauser Flowphant T DTT31 Technical Information

Flow switch for safe monitoring of mass flow and temperature in industrial processes
Hide thumbs Also See for Flowphant T DTT31:

Advertisement

Technical information

Flow switch
®
Flowphant
Flow switch for safe monitoring of mass flow and temperature in
industrial processes
TI00125R/09/en
71009492
T DTT31, DTT35
Application
Flow switch for monitoring and displaying relative mass flow
rates of liquid media in the range from
0.03 to 3 m/s (0.1 to 9.84 ft/s):
®
Flowphant
T DTT31
− with thread connections or coupling
®
Flowphant
T DTT35
− with process connections for hygienic applications
Application examples:
• Monitoring cooling water circulation systems of pumps,
turbines, compressors and heat exchangers
• Monitoring pump functionality
• Leak monitoring in process lines
• Monitoring lubrication systems
• Filter monitoring in the beverage industry
Benefits at a glance
This compact flow switch impresses with the latest in
technology being used:
• Practically no pressure loss
• Configuration software ReadWin
quick configuration and reliable storage of device settings
• Optional: 4 to 20 mA analog output to read out the flow rate
as percentage value
• Optional: second switch output or 4 to 20 mA analog output
for temperature monitoring
• Function check and process information onsite thanks to
digital display at device
• Top housing section which can be rotated 310° and rotatable
display make it possible to read the measured values in all
orientations
• DTT35: 3-A marked
®
2000 or FieldCare for

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Flowphant T DTT31

  • Page 1: Technical Information

    Technical information Flow switch ® Flowphant T DTT31, DTT35 Flow switch for safe monitoring of mass flow and temperature in industrial processes Application Flow switch for monitoring and displaying relative mass flow rates of liquid media in the range from 0.03 to 3 m/s (0.1 to 9.84 ft/s): ®...
  • Page 2: Function And System Design

    − ANSI NPT ¼" and NPT ½" − Varivent F, N − DIN 11851 − APV-Inline Measuring range Mass flow as a relative value between 0 and 100%. Process measuring limit, liquids: 0.03 to 3 m/s (0.1 to 9.84 ft/s) Endress+Hauser...
  • Page 3 If you would like to read off the instantaneous value of the temperature not only locally, but also record, analyze and display it e.g. directly from a control room or in the PC network, then the following devices are suitable: Endress+Hauser...
  • Page 4 Automatic testing of switching current; output is switched off in case of overcurrent, the switching current is tested again every 0.5 s; max. capacitance load: 14 μF for max. supply voltage (without resistive load) Periodic disconnection from a protective circuit in event of overcurrent (f = 2 Hz) and indication of ’Warning’ Endress+Hauser...
  • Page 5: Power Supply

    1x PNP switch output DTT3x-A1A******* 2x PNP switch output R1 and m (R2) DTT3x-A1B******* 2x PNP switch output R1 and m (diagnosis/NC A2’ DTT3x-A1B******* contact with "DESINA" setting) 1x PNP switch output and 1x analog output DTT3x-A1C******* (4 to 20 mA) Endress+Hauser...
  • Page 6: Performance Characteristics

    An absolute measurement of the fluid velocity or the mass flow is not possible. The sensitivity of the calorimetric flow sensor changes with the fluid velocity. It increases with decreasing fluid velocity (for example, with water, the greatest sensor sensitivity is recorded in the range from 0.03 to 0.5 m/s). Endress+Hauser...
  • Page 7 (calculated according to "British Telecom Handbook of Reliability Data No. 5") Switch output response time 100 ms Analog output • Maximum measured error = switch point error and display error + 0.1% : ≤ 200 ms • Rise time T : ≤ 500 ms • Settling time T Endress+Hauser...
  • Page 8: Operating Conditions: Installation Instructions

    No restrictions, but self draining. Inlet and outlet run The sensor requires a fully developed flow profile for correct monitoring. For this reason, steadying sections (5x DN) must be provided in the pipe after a pump, pipe bend, internal fittings and cross-sectional changes. Endress+Hauser...
  • Page 9: Operating Conditions: Environment

    The maximum process pressure for the conical metal-metal process connection (MB option) for the DTT35 is 1.6 MPa = 16 bar (232 psi)! Process flow limit Liquids: 0 up to 3.0 m/s (0 up to 9.84 ft/s) Operating range Liquids: 0.03 up to 3.0 m/s (0.1 up to 9.84 ft/s) Endress+Hauser...
  • Page 10: Mechanical Construction

    • 19 mm (0.75 in) • 8.1 mm (0.32 in) Cylindrical threaded process connection in inches as per ISO 228: • G¼" (n = AF14) • 12 mm (0.47 in) • G½" (n = AF27) • 14 mm (0.55 in) Endress+Hauser...
  • Page 11: Dtt35 Design, Dimensions For Process Connections

    O ring between housing and sensor modul: EPDM • Electrical connection: M12 connector: exterior AISI 316L, interior polyamide (PA) Valve plug: outer polyamide (PA) M12 connector: exterior 316L Cable outer covering: polyurethane (PUR) O ring between electrical connection and housing: FKM Endress+Hauser...
  • Page 12: Human Interface

    DESINA. (DESINA = DistributEd and Standardized INstAllation technology for machine tools and manufacturing systems) CAL (calibration) Learn High Flow (HIF) Setting for maximum flowrate occurring. 100% value Learn Low Flow (LOWF) Setting for minimum flowrate occurring. 0% value Endress+Hauser...
  • Page 13 Locking, only visible with valid operating code. Device status (STAT) Last error (LSTA) Display of last error to occur. Simulation: Simulation 1 (SIMU) Simulation switch output 1: on/off with display, switch output version Simulation 2 (SIM2), optional optionally corresponding to switch output 2. Endress+Hauser...
  • Page 14: Switch-Point Function

    FieldCare provides further information on the Flowphant Function group Function (display) Description SERV Switching processes 1 Number of changes in switching status for (service functions) Switching processes 2, switch output 1; optionally switch output 2 optional Endress+Hauser...
  • Page 15: Certificates And Approvals

    Software revision Software version Certificates and approvals CE-Mark The device meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has been successfully tested by applying the CE mark. Ship building approval (Germanischer Lloyd) Other standards and •...
  • Page 16: Ordering Information

    This information provides an overview of the order options available. The information is not exhaustive, Product structure however, and may not be fully up to date. More detailed information is available from your local Endress+Hauser representative. ® Flowphant T DTT31 Flow switch, intelligent, programmable.
  • Page 17 This information provides an overview of the order options available. The information is not exhaustive, product structure however, and may not be fully up to date. More detailed information is available from your local Endress+Hauser representative. ® Flowphant T DTT35 Flow switch, intelligent, programmable.
  • Page 18 Material of parts in contact with process: 316L/ 1.4435 Max. process pressure 16 bar (232 PSI) Order number: 60021387 a0006621 Coupling Coupling M12x1 for simple user installable assembly of the connecting cable; straight connection to M12x1 housing connector Order number: 52006263 P01-PMP13xxx-00-xx-00-xx-003 Endress+Hauser...
  • Page 19 Configuration software • ReadWin 2000 and FieldCare ’Device Setup’ can be downloaded free of charge directly from the internet at the following addresses: www.endress.com/readwin www.products.endress.com/fieldcare For the order of the FieldCare ’Device Setup’ software please ask your Endress+Hauser sales organisation. Endress+Hauser...
  • Page 20 Power supply • Power supply Easy Analog RNB130 by Endress+Hauser with nominal output current I = 1.5 A. Ν Details see Technical information TI120R/09/en. • Process display RIA452 by Endress+Hauser with transmitter power supply, max. output current I = 250 mA.