Additional Features; Operating Environmental Conditions; Alarm Transmitter Equipment (Ate) Specification - DSC Neo Power Series Installation Manual

Alarm controller
Hide thumbs Also See for Neo Power Series:
Table of Contents

Advertisement

Bell Output:
12V, 700mA supervised (1k Ohm) bell output (current limited at
l
2 amps)
Steady, Pulsed, Temporal 3 fire, CO alarm cadences
l
Bell short detection (software + hardware)
l
Aux+:
Voltage range = 9.6V - 13.8V DC
l
Current = 700mA (shared with PGM outputs)
l
Output ripple voltage: 270mVp-p max.
l
Onboard programmable outputs:
l
PGM 1 - 50mA switched programmable output
l
PGM 2 - 300mA current-limited switched programmable
l
output. 2-Wire smoke detectors (90mA current limited)
are supported using this PGM
PGM 3 - 50mA switched programmable output
l
PGM 4 - 50mA switched programmable output
l
Hardware PGM over current protection
l
Battery
12V sealed lead acid, rechargeable
l
Battery capacity:
l
4Ah (PS4-12)
l
7Ah (BD7-12)
l
14Ah
l
Maximum standby time: 24 hours (with 14Ah battery and Aux
l
current limited to 470mA)
Recharging time to 80% 72 hours
l
Recharging rate: 240mA (12 hours max.), 480mA (24 hour
l
backup)
Backup time: 24 hours (UL)
l
Battery lifespan: 3-5 years
l
Low battery trouble indication threshold 11.5VDC
l
Battery restore voltage 12.5V
l
Main board current draw (battery only):
l
HS2016/32/64/128 (no alternate communicator) standby
l
85mA DC
HS2016/32/64/128, (including alternate communicator)
l
standby 190mA DC
Transmit (alternate communicator module) 195mA DC
l
Resettable fuses (PTC) used on circuit board
l
Supervision for loss of primary power source (AC fail), battery
l
loss or battery low voltage (battery trouble) with indication
provided on the keypad
Internal clock locked to AC power frequency
l

Operating Environmental Conditions

Temperature range: UL= 0°C to +49°C (32°F-120°F),
l
Relative humidity: <93% non condensing
l

Alarm Transmitter Equipment (ATE) Specification

Digital dialer integral to the main control board
l
Supports SIA and Contact ID
l
Complies with TS203 021-1, -2, -3 Telecom equipment require-
l
ments and EN50136-1-1, EN50136-2-1, EN50136-2-3 ATS 2
Optional Dual IP/Cellular communicators (3G2080(R)/ TL2803G
l
(R)/ TL280(R)) can be installed in the same enclosure and con-
figured as primary or back-up, with AES 128-bit encryption
Compliant with EN50136-1-1, EN50136-2-1 ATS2 requirements
l
System Supervision Features
The PowerSeries Neo continuously monitors a number of possible trouble
conditions and provides audible and visual indication at the keypad.
Trouble conditions include:
AC power failure
l
Zone trouble
l
Fire trouble
l
PowerSeries Neo Installation Guide
Telephone line trouble
l
Communicator trouble
l
Low battery condition
l
RF jam
l
AUX power supply fault
l
Failure to communicate
l
Module fault (supervisory or tamper)
l

Additional Features

2-way wireless device support
l
Visual verification (images + audio)*
l
Proximity tag support
l
PGM scheduling
l
Quick arming
l
User, partition, module, zone and system labels
l
Soak test*
l
Programmable system loop response
l
Keypad and panel software versions viewable through keypad
l
Doorbell zone type
l
Low battery PGM type
l
*Feature not evaluated by UL/ULC.
- 10 -