DSC Neo Power Series Installation Manual page 26

Alarm controller
Hide thumbs Also See for Neo Power Series:
Table of Contents

Advertisement

For a list of the default values programmed when the unit is shipped from
the factory, and for any other programming information, refer to the
following table.
The following optional subassembly modules also bear the SIA CP-01-
2010 classification and may be used if desired: HSM2108 zone expander,
HSM2208 PGM output module, HSM2300 auxiliary power supply,
HSM2204 output module, HSM2HOST9 2-way wireless transceiver,
PG9901 indoor siren, PG9911 outdoor siren, and 3G2080(R)/ TL2803G
(R)/ TL280(R) cellular and PSDN communication module.
Caution
For SIA FAR installations use only modules/devices that are lis-
l
ted on this page.
Fire Alarm Verification feature (Auto Verified Fire Zone type
l
[025]) is not supported on 2-wire smoke detectors zones, model
FSA-210B(T)(S)(ST)(LST)(R)(RT)(RD)(RST)(LRST). This fea-
ture may be enabled for 4-wire smoke detectors only (FSA-410B
(T)(S)(ST)(LST)(R)(RT)(RST)(LRST) and wireless detectors
PG9916/PG9926). The fire alarm delay is 60s.
Call Waiting Cancel (Section [382], Option 4) feature on a non-
l
Call Waiting line will prevent successful communication to the
supervising station.
All smoke detectors on the system must be tested annually by con-
l
ducting the Installer Walk Test. Prior to exiting walk test mode, a
sensor reset must be done on the system, [*][7][2], to reset all
latching 4-wire smoke detectors. Refer to the installation instruc-
tions supplied with the detector for details.
Notes
Programming at installation may be subordinate to other UL
l
requirements for the intended application.
Cross zones have the ability to individually protect the intended
l
area (e.g. motion detectors which overlap).
Cross zoning is not recommended for line security Installations
l
nor is it to be implemented on exit/entry zones.
This control panel has a communication delay of 30 seconds. It
l
can be removed or increased up to 45 seconds by the end user in
consultation with the installer.
The security system shall be installed with the sounding device
l
activated and the communicator enabled for transmission using
SIA or CID format.
ULC commercial burglary installations require DEOL resistors.
l
PowerSeries Neo Installation Guide
- 26 -