Figure 5-6: Industrial Relay Card-MS
5.2 Intelligent Power Software
Intelligent Power Software are productivity tools for UPS power management. The Intelligent Power Protector
(IPP) application provides automatic, graceful shutdown of computers and virtual machines or servers
powered by an Eaton UPS during a power outage that lasts longer than your available battery runtime.
Intelligent Power Protector can be remotely supervised and managed by the Intelligent Power Manager (IPM)
application. The IPM delivers a global view of power devices across the network from any PC with an Internet
browser. The software enables single, Web-based interface for remote monitoring and management of Eaton
and other manufacturers' UPSs, environmental sensors and Power Distribution Units (ePDU) products, even
in virtualized environments.
The Intelligent Power Software is delivered on a CD with the UPS. Alternatively, you can download it from the
Eaton web page.
5.3

Signal input Monitoring

This standard feature lets you connect the UPS to your signal inputs, such as smoke detectors or
overtemperature alarms. The customer interface terminals for external connections are located inside the
UPS. You should use twisted-pair wires for each alarm input and common.
The signal inputs can be programmed to display the alarm functional name.
5.4

General Purpose Relay Contact

One general purpose relay contact is provided as a standard feature on the UPS. An alarm contact is also
provided. You can use a normally-closed or normally-open contact. If the state of the contact changes from
the state you specify as normal, a signal is issued. You can connect this contact to equipment at your facility
(such as a light or an alarm bell) to let you know when an alarm is active on the UPS. This feature is useful if
the UPS is located in a remote area where the UPS horn may not be heard immediately.
Contacts should not be operated in excess of 30 VAC (RMS) and 30 VDC at 5 A maximum.
NOTE
25-75 kW
User's and Installation Guide
54