Ups System Output; Table 8-3. Ups System Output - Eaton 93PR Series User And Installation Manual

Table of Contents

Advertisement

8.3

UPS System Output

Table 8-3: UPS System Output
Number of Output Phases
Rated Output Voltage
Total Voltage Harmonic distortion
100 % Linear Load
100 % Non-Linear Load
Rated Output Frequency
Output Frequency Variation
Slew Rate
Overload Capability at Ambient 40 °C
(on Inverter)
Overload Capability at Ambient 40 °C
(on Inverter, Stored Energy Mode)
Overload Capability at Ambient 40 °C
(on Bypass)
Output Current
Load Power Factor, (Rated)
Load Power Factor, (Permitted Range)
81
3 phases + N
220/380 V; 230/400 V; 240/415 V, configurable
< 1 %
< 5 %
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
10 min 105-110 % load
60 sec 111-125 % load
10 sec 126-150 % load
300 ms > 150 % load
10 min 105-110 % load
60 sec 111-125 % load
300 ms > 126 % load
Continuous < 125 % load
10 ms 1000 % load
Note! Bypass fuses may limit the overload capability.
See Table 3-7: Rated and maximum currents for rated
power and voltage on page 31
1.0
From 0.8 lagging to 0.8 leading
25-75 kW
User's and Installation Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

93pr 50(75)93pr 75(75)93pr 25(75)

Table of Contents