5.4 Program Functions
5.4.6
Other Functions
These other functions [Program Repeat, Power Failure Option, and Program Start from
PV] are set through the SETS function (Refer to Table 4-4 Functions of Sets).
SET
8.1
8.2
8.3
8/05
(continued)
Table 5-2 Associated Program Functions
Function
0 = No Program Repeat
1 = Program Repeats
0 = No Power Failure Option
1 = With Power Failure Option
0 = Program starts from 0
1 = Program starts from PV
DC1010/1020/1030/1040 Product Manual
Programmer (Optional)
Remarks
When SET 8.1 = 1, the program will repeat
from beginning to end.
When SET 8.2 = 1, if power is lost before
the "target" setpoint is reached, upon power
recovery, the controller powers up with
Setpoint = Current PV value and it
automatically "Restarts" from setpont =
current PV value up to the original "target"
setpoint.
When SET 8.3 = 1, the setpoint is set to the
current PV value and the Program then
starts from this value. The program will be
more energy efficient, and also decrease
the time needed to achieve the desired
setpoint value. The remaining time left to
reach the setpoint value will be shown in the
parameter "TIMR" (See Table 5-3 Program
Configuration Prompts). The time of
countdown in this instance is related to the
PV value, not the segment setting.
43