Configuration

4.1 Introduction

Configuration is a dedicated operation where you use straightforward keystroke
sequences to select and establish (configure) pertinent control data best suited for your
application. To assist you in the configuration process, there are prompts that appear in
the upper and lower displays. Refer to Figure 3-1

4.2 Configuration 1

To access 'Configuration 1' mode, press the 'SET' key for 5 seconds while in
'Operation' mode (Section 3.4)
Displays
Default Value
Shown
Main Control (OUT 1)
.
. .
P Value (Proportional Band)
SET
SET
SET
SET
SET
SET
SET
SET
Main Control (OUT 1)
I Value (Integral Value)
SET
SET
Main Control (OUT 1)
D Value (Derivative Time)
SET
SET
Main Control
Dead-Band Time
SET
SET
Main Control (OUT 1)
Auto Tuning Offset
SET
SET
For Programmer models-
ATVL means Auto Tuning
Point.
24
4 Configuration

Table 4-1 Configuration 1 Mode

Parameter
Proportional - Regulates the controller's output in
proportion to the error signal (the difference between
Process Variable and Setpoint).Range: 0 – 200%
Integral - Regulates the controller's output to the size of
the error and the time the error has existed. (The
amount of corrective action depends on the value of
proportional Gain.)
Range: 0 – 3200 seconds
Integral off, I = 0
Derivative – Regulates the controller's output in
proportion to the rate of change of the error. (The
amount of corrective action depends on the value of
proportional Gain.)
Range: 0 – 900 seconds
Derivative off, D = 0
* DO NOT CHANGE THE VALUE
Range: 0 – Upper Limit Value (USPL)
Prevents Overshoot during Autotuning
DC1010/1020/1030/1040 Product Manual
Description
[For On/Off Control, set P1 = 0. The only other
prompt required for setting is HYS 1]