Installer Manual Fleck 5800 - XTR - Troubleshooting
Error screen
display
Flow meter error
Continuous Flow
Over current
Motor drew too much
Motor over current
detected
Flow meter error
No flow detected
No regeneration
for 100 days
Service Interval
controller has expired.
Memory
Corruption Error
Motor Stall
Motor Run-On
No changes
the optical sensor are
detected in the
optical sensor for
6 seconds
108 / 122
Cause
The flow meter has
reported continuous
flow for more than
24 hours.
current.
No flow has been
detected for 7 days.
The valve has not
regenerated in more
than 100 days.
Service Interval
Internal memory
inconsistent or
corrupted.
No state changes in
detected for
six seconds.
Reset and recovery
Error will clear when flow to meter drops below 0.5
GPM or 1 LPM. If continuous flow is expected, turn
plumbing leak detection off in Master Settings.
Attempt to perform a manual regeneration. If error
continues, call technical support.
Error will clear when a flow pulse is detected. Check to
ensure meter cable is properly installed and meter
spins freely. Clear meter of debris if necessary. If error
continues, call technical support.
Initiate a regeneration see "Troubleshooting",
page 105.
From within Master Settings, navigate to the
Assistance/Mainten. Interval screen and set a new
Service Interval time.
1. Cycle power to XTR2 controller.
2. Drain supercap and cycle power to XTR2 controller.
3. If error continues, call technical support.
Unplug the unit and plug back in. Allow the control to
attempt to find position again.
Verify the optical sensor is in place with the wires
connected to the circuit board. Verify the motor and
drive train components are in good condition and
assembled properly. Check the valve and verify that the
piston travels freely. Replace/reassemble the various
components as necessary.
Plug the unit back in and observe its behaviour. If the
error reoccurs, unplug the unit, put it into bypass and
contact technical support.
Ref. MKT-IM-006 / B - 16.01.2018