11.6.13 Step 13, change the parameters of the operator interface

Change the processing of "Fire alarm condition"
Select
Option
Function
KEY13
"Fire alarm" also in state "Manual only":
LED6 = lit in steady mode, LED7 = flashing fast
1 (default)
Active: Horns, monitored control lines and outputs programmed as
activated on fire alarm condition
No "Fire alarm" in state "Manual only":
LED6 = lit in steady mode, LED7 = OFF
2
Not active: Horns, monitored control lines and outputs programmed
as activated on fire alarm condition
Change the function of the key "Silence buzzer" (KEY15)
Select
Option
Function
KEY13
3 (default)
Only for "Silence buzzer" in state "Fire alarm"
4
For "Silence buzzer" and "Silence Re-sound horn" in state "Fire alarm"
Enable the function "Reminder beep"
Select
Option
Function
KEY14
5 (default)
No reminder beep
6
Buzzer sounds every 4 min for 1 sec in case of "Fault" or "Disabled"
Enable the function "Fault to be reset"
Select
Option
Function
KEY14
7 (default)
Faults must not be reset
8
All faults must be reset
Enable the function "RT-alarm + RT-fault suppressed on access level 2"
Select
Option
Function
KEY15
9 (default)
No blocking
10
"RT-alarm" and "RT-fault" disabled on state "Access level 2 enabled"
Enable the function "Reset via control input 1 suppressed upon RT-alarm"
Select
Option
Function
KEY15
11 (default) Not blocked
12
Blocked on state "RT-alarm"
Suppress the "Battery fault"
Select
Option
Function
KEY16
13 (default) Battery fault not suppressed
14
Battery fault suppressed
Change the active mode of the buzzer in state "Emergency hold/abort"
Select
Option
Function
KEY16
15 (default) 1 sec beep with begin and end of state "Emergency hold/abort"
16
Active until key "Silence buzzer" is pressed
Building Technologies
Fire Safety & Security Products
Programming the user functions
Zone 1
Zone 2
Zone 3
Red
Yel. Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red
Yel.
Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red
Red Yel.
Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel. Red
Yel.
Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red
Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Yel.
Red Yel. Red
Yel. Red
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel. Red
A6V10099837_a_en
Zone 4
Zone 4
Zone 4
Zone 4
Zone 4
Zone 4
Red Yel.
Zone 4
Red
Yel.
Zone 4
Yel.
87
12.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents