Connection elements
The specified conductor cross sections describe the capacity of the connection terminals.
When selecting the conduction cross sections, always pay attention to the possible current
load and ensure adequate cable protection.
Current, power supply
Conductor cross section
2-wire, same cross-section
AWG
Tightening torque
Communication ports
Conductor cross section
2-wire, same cross-section
AWG
Tightening torque
PAC2200
Manual, 05/2018, L1V30415167B-02
Rigid
Flexible
Flexible with end sleeve, without plastic
sleeve
Flexible with end sleeve and plastic
sleeve
AWG
Rigid
Flexible
Flexible with end sleeve, without plastic
sleeve
Flexible with TWIN end sleeve and plastic
sleeve
Rigid
Flexible
Flexible with end sleeve, without plastic
sleeve
Flexible with end sleeve and plastic
sleeve
AWG
Rigid
Flexible
Flexible with end sleeve, without plastic
sleeve
Flexible with TWIN end sleeve and plas-
tic sleeve
5 A device
0.2 ... 6 mm
2
0.2 ... 4 mm
2
0.2 ... 4 mm
2
0.25 ... 4 mm
2
24 ... 10
0.2 ... 1.5 mm
2
0.2 ... 1.5 mm
2
0.25 ... 0.75 mm
2
0.5 ... 2.5 mm
2
24 ... 14
0.5 ... 0.6 Nm [4.4
...5.3 lb-in]
0.14 ... 1.5 mm
2
0.14 ... 1.5 mm
2
0.25 ... 1 mm
2
0.25 ... 1.5 mm
2
26 ... 16
0.14 ... 0.75 mm
2
0.14 ... 0.75 mm
2
0.25 ... 0.5 mm
2
0.5 ... 1 mm
2
26 ... 18
0.5 ... 0.6 Nm [4.4 ...5.3 lb-in]
Technical data
8.1 Technical data
65 A device
0.75 ... 35 mm
2
1 ... 35 mm
2
0.75 ... 25 mm
2
0.75 ... 25 mm
2
19 ... 2
0.75 ... 10 mm
2
1 ... 4 mm
2
0.75 ... 4 mm2
0.75 ... 4 mm
2
19 ... 8
3 Nm [26.6 lb-in]
79