Siemens SENTRON PAC2200 Product Manual page 102

7km measuring device
Hide thumbs Also See for SENTRON PAC2200:
Table of Contents

Advertisement

Appendix
A.1 Modbus TCP
Table A- 9
Settings parameter for the digital output
Offset
Number of
registers
50033
2
50035
2
50041
2
50043
2
50045
2
50147
2
50237
2
100
Name
Switching function as-
signment to a vector
group
Digital output "Action"
"Energy pulse" mode
Pulses per unit (pulses
per 1000 Wh / VARh)
Pulse length
Digital output timeout
Output pulse divider
Unit
Format
-
unsigned long
-
unsigned long
-
unsigned long
-
unsigned long
ms
unsigned long
s
unsigned long
kWh
unsigned long
Value range
0 ... 99
0 =
Off
1 =
Device ON
2 =
Switching output
3 =
Phase sequence
5 =
Energy pulse
0 =
Import kWh
1 =
Export kWh
2 =
Import kVARh
3 =
Export kVARh
1 ... 4000
30 ... 500
0 = AUS
0.1 ... 18000 = Output is
reset after expiry of the
time, provided there is no
operator input.
0 =
1 kWh
1 =
10 kWh
2 =
100 kWh
3 =
1000 kWh
Manual, 05/2018, L1V30415167B-02
Access
RW
RW
RW
RW
RW
RW
RW
PAC2200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents