Averaging Measured Values - Siemens SENTRON PAC2200 Product Manual

7km measuring device
Hide thumbs Also See for SENTRON PAC2200:
Table of Contents

Advertisement

Measured variable
L2 reactive energy export tariff 2
L2 apparent energy tariff 1
L2 apparent energy tariff 2
L3 active energy import tariff 1
L3 active energy import tariff 2
L3 active energy export tariff 1
L3 active energy export tariff 2
L3 reactive energy import tariff 1
L3 reactive energy import tariff 2
L3 reactive energy export tariff 1
L3 reactive energy export tariff 2
L3 apparent energy tariff 1
L3 apparent energy tariff 2
Secondary total active energy (MID register)
2.3

Averaging measured values

With appropriate load profiles, consumers can carry out a targeted optimization of their
energy consumption.
Instantaneous values are averaged over specific time periods to create load profiles. For this
purpose, measured values are read out via the communication and stored. This
increases the bus load considerably and occupies storage capacity.
The PAC2200 device has two average value generators, which can be parameterized
independently.
The aggregation of the measured values reduces the bus load without risk of loosing
information. Average values are calculated contiguously, based on the underlying values.
The values are updated each time after expiry of the set time period.
The default setting for average value 1 is a period length of 10 seconds.
The default setting for average value 2 is a period length of 15 minutes.
The period length can be set to anything between 3 seconds and 31536000 seconds (1
year).
This function is only available if communication interfaces via Modbus TCP/RTU are used.
The list of available measured values can be found in the appendix A.1.4 „Modbus variables
with function code 0x14" on page 82 (Page 92).
PAC2200
Manual, 05/2018, L1V30415167B-02
2.3 Averaging measured values
Connection type
3P4W
Description
1P2W
19