5. Operation

5.7 Configuration Options via WEBCARDLX

CONTROL
DEVICE
Setting
Auto Batt. Testing
(Set regular battery
self-test interval)
Reset to Factory
Settings
CONFIGURATION
Property
Audible Alarm
Output Voltage
Power Strategy
Cold Start
Auto-Restart
Auto-Restart Delay • Enter: 0 to 60 seconds
Energy Saving
Off Mode
18-09-247-933652.indb 15
Value(s)
• Disable
• 4 weeks (factory setting)
• 13 weeks
• 26 weeks
• Factory Reset
DEVICE SETTINGS
Value(s)
• Enable
• Disable
• 200
• 208
• 220
• 230
• 240
• Auto-Adaptive (factory setting)
• Max Efficiency
• Max Quality
• Freq. Regulation
• Freq. Conversion to 60Hz
• Freq. Conversion to 50Hz
• Enable (factory setting)
• Disable
• Enable (factory setting)
• Disable
(factory setting is 0 seconds)
• Enter: 0-100%
• Disable (factory setting)
• Standby
• Bypass (factory setting)
Description
Use this option to initiate automatic UPS
battery testing at regular intervals.
Use this option to reset all UPS
preferences to factory settings, including
battery configurations.
DEVICE PROPERTIES
Description
Audible Alarm DISABLE setting prevents
power fail and operating fault alarms only;
the UPS will always "beep" to confirm the
UPS is accepting user input.
Use this option to set the nominal UPS
output voltage (changes take effect on
next restart).
Use this option to set the UPS Power
strategy.
See Section 5.3: Power Strategy
Selection Options under Operations
for more info on available Power Strategy
options.
Enabling Cold Start allows the UPS to be
manually turned on into battery mode
during a power failure.
Enabling Auto-Restart allows the UPS to
automatically turn back on into a protected
operating mode when power is restored.
Auto-Restart delay forces the UPS to wait
0-60 seconds after power is restored
before automatically restarting. Requires
that Auto-restart be enabled when power
is restored.
Energy Saving enables the UPS to
automatically shutdown when the output
load is less than the selected percentage
continuously for 5 minutes.
Off Mode setting of BYPASS allows the
UPS to provide unregulated line power
within configured bypass low / high limits
to be available at the output of the UPS
when it is turned off.
15