5. Operation
CONFIGURATION
Threshold
Overload Alert Lvl.
Conf. Fault Action
(UPS response to
fault)
Bypass Low Limit
Bypass High Limit
18-09-247-933652.indb 17
DEVICE SETTINGS
Value(s)
• Enter: 5-105%
(factory setting is 100%)
• Go to bypass (factory setting)
• Go to standby
• Enter: -5% to -20%
(factory setting is -15%)
• Enter: +5% to +20%
(factory setting is +10%)
DEVICE THRESHOLDS
Description
Sets the UPS output load percentage before
an overload alert is sent.
Sets the UPS response to fault conditions
that require the UPS to exit double-
conversion mode. GO TO BYPASS option
maintains AC output (so long as input
voltage is within bypass high/low limits). GO
TO STANDBY option causes the UPS to turn
off output AC in response to fault conditions.
Specifies the lowest acceptable input
voltage for bypass operation.
Specifies the highest acceptable input
voltage for bypass operation.