5. Operation

5.8 Configuration Options via WEBCARDLX

CONTROL
DEVICE
Setting
Auto Batt. Testing
(Set regular battery
self-test interval)
Reset to Factory
Settings
CONFIGURATION
Property
Audible alarm
Output Voltage
Power Strategy
Cold Start
Auto-Restart
Auto-Restart Delay Enter: 0 to 60 seconds
Energy Saving
Off Mode
17-04-276 9335AA.indb 16
Value(s)
• Disable
• 4 weeks (factory setting)
• 13 weeks
• 26 weeks
• Factory Reset
DEVICE SETTINGS
Value(s)
• Enable
• Disable
• 100
• 110
• 115
• 120
• 127
• Auto-Adaptive (factory setting)
• Max Efficiency
• Max Quality
• Freq. Regulation
• Freq. Conversion to 60Hz
• Freq. Conversion to 50Hz
• Enable (factory setting)
• Disable
• Enable (factory setting)
• Disable
(factory setting is 0 seconds)
• Enter: 0-100%
• Disable (factory setting)
• Standby
• Bypass (factory setting)
Description
Use this option to initiate automatic
UPS battery testing at regular
intervals.
Use this option to reset all UPS
preferences to factory settings,
including battery configurations.
DEVICE PROPERTIES
Description
Audible Alarm DISABLE setting
prevents power fail and operating
fault alarms only; the UPS will
always "beep" to confirm the UPS is
accepting user input.
Use this option to set the nominal
UPS output voltage (changes take
effect on next restart).
Use this option to set the UPS Power
strategy.
See Section 5.3: Power Strategy
Selection Options under
Operations for more info on available
power strategy options.
Enabling Cold Start allows the UPS
to be manually turned on into battery
mode during a power failure.
Enabling Auto-Restart allows the UPS
to automatically turn back on into
a protected operating mode when
power is restored.
Auto-Restart delay forces the UPS
to wait 0-60 seconds after power
is restored before automatically
restarting. Requires Auto-Restart be
enabled when power is restored.
Energy Saving enables the UPS to
automatically shutdown when the
output load is less than the selected
percentage continuously for 5
minutes.
Off Mode setting of BYPASS allows
the UPS to provide unregulated line
power within configured bypass
low / high limits to be available at the
output of the UPS when it is turned
off.