Installation; Limitations; Location; Product Nomenclature - York AFFINITY Series Installation Manual

Single packaged gas/electric air cooled air conditioners 2, 2-1/2, 3, 3-1/2, 4 and 5 nominal ton
Hide thumbs Also See for AFFINITY Series:
Table of Contents

Advertisement

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the follow-
ing national and local safety codes.
1.
National Electrical Code ANSI/NFPS No. 70 or Canadian
Electrical Code Part 1, C22.1 (latest editions).
2.
National Fuel Gas Code Z223.1 or CSA B149.1 Installa-
tion Code.
3.
Local gas utility requirements.
PRODUCT CATEGORY
D = Single Package Air Conditioner
PRODUCT GENERATION
1 = 1st Generation
2 = 2nd Generation
3 = 3rd Generation
PRODUCT IDENTIFIER
NP = 13 SEER Gas Heat/Electric
FIGURE 1 - PRODUCT NOMENCLATURE
TABLE 1: UNIT APPLICATION DATA
208/230V
Voltage Variation
1
Min. / Max.
Wet Bulb Temperature (°F) of Air on
Evaporator Coil, Min. / Max.
Dry Bulb Temperature (°F) of Air on
Condenser Coil, Min.
1. Rated in accordance with ARI Standard 110, utilization
range "A".
2. "T1" transformer primary tap must be moved from the
230 volt connection to the 208 volt connection for low
voltage applications of 208 volt and below
3. A low ambient accessory is available for operation
down to 0 °F.

LOCATION

Use the following guidelines to select a suitable location for
these units.
Johnson Controls Unitary Products
D
1
N P
NOMINAL COOLING
CAPACITY (MBH)
024 = 24,000 BTUH
030 = 30,000 BTUH
036 = 36,000 BTUH
042 = 42,000 BTUH
048 = 48,000 BTUH
060 = 60,000 BTUH
2
187 / 252
460V
432 / 504
575V
540 / 630
57 / 72
45 / 120
3
/ Max.
4.
Local plumbing and waste water codes and other appli-
cable local codes.
Refer to Table 1 for unit application data and to Tables 3 thru
6 for gas heat application data.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning
Contractors of America.
0
3
6
N
0
3
6
NOMINAL HIGH GAS HEAT OUTPUT CAPACITY
(NOMINAL LOW GAS HEAT OUTPUT CAPACITY)
036 = 36,000 BTUH
FACTORY INSTALLED
056 = 56,000 BTUH (36,400 BTUH)
NATURAL GAS HEAT
065 = 65,000 BTUH
072 = 72,000 BTUH (46,800 BTUH)
N = Single Stage
090 = 90,000 BTUH (56,160 BTUH)
D = Two Stage
110 = 110,000 BTUH (70,200 BTUH)
1.
Unit is designed for outdoor installation only.
2.
Condenser must have an unlimited supply of air. Where
a choice of location is possible, position unit on either
north or east side of building.
Excessive exposure of this furnace to contami-
nated combustion air may result in equipment
damage or personal injury. Typical contaminates
include: permanent wave solution, chlorinated
washes and cleaners, chlorine based swimming
pool chemicals, water softening chemicals, carbon
tetrachloride, halogen type refrigerants, cleaning
solvents (e.g. perchloroethylene), printing inks,
paint removers, varnishes, hydrochloric acid,
cements and glues, antistatic fabric softeners for
clothes dryers, masonry acid washing materials.
280241-YIM-D-0909
0
6
VOLTAGE CODE
06 = 208/230-1-60
25 = 208/230-3-60
46 = 460-3-60
58 = 575-3-60