1
TABLE 5: PROPANE
(LP) GAS APPLICATION DATA - SINGLE STAGE
INPUT
AVAILABLE ON
MODELS
(MBH)
2, 2-1/2, 3 TON
45
2, 2-1/2 TON
70
3 TON
70
3-1/2, 4, 5 TON
80
3 TON
90
3-1/2 TON
108
4, 5 TON
108
4, 5 TON
135
1. Propane applications are accomplished by field installation of a Propane Conversion Accessory, Model 1NP0807 for 2 thru 3 Ton
units with 33-1/2" tall cabinets and Model 1NP0808 for 3-1/2 thru 5 Ton units with 41-1/2" tall cabinets.
2. Heating capacity valid for elevations up to 2,000 feet above sea level. For elevations above 2,000 feet, rated capacity should be
reduced by 4% for each 1,000 feet above sea level.
3. Based on 2500 BTU/Ft.
4. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperatures should not
be below 55°F.
1
TABLE 6: PROPANE
GAS APPLICATION DATA - TWO STAGE
AVAILABLE ON
INPUT (MBH)
MODELS
HIGH FIRE / LOW FIRE
2, 2-1/2TON
3 TON
3 TON
4, 5 TON
108 / 70.2
4, 5 TON
135 / 87.75
1. Propane applications are accomplished by field installation of a Propane Conversion Accessory, Model 1NP0809 for 2 thru 3 Ton
units with 33-1/2" tall cabinets and Model 1NP0810 for 4 and 5 Ton units with 41-1/2" tall cabinets.
2. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be
reduced by 4% for each 1,000 feet above sea level.
3. Based on 2500 BTU/Ft.
4. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not
be below 55°F.
Johnson Controls Unitary Products
OUTPUT
2
(MBH)
36
56
56
64
72
87
87
108
3
.
2
OUTPUT (MBH)
HIGH FIRE/LOW FIRE
70 / 45.5
56 / 36.4
70 / 45.5
56 / 36.4
90 / 58.5
72 / 46.8
87 / 56.2
108 / 70.2
3
.
3
GAS RATE
NUMBER OF
3
BURNERS
FT.
/HR.
18
28
28
32
36
43
43
54
3
GAS RATE
HIGH FIRE/LOW FIRE
28 / 18.2
28 / 18.2
36 / 23.4
43 / 27.95
54 / 35.1
280241-YIM-D-0909
TEMP. RISE ºF AT
FULL INPUT
MIN.
2
25
3
30
3
25
3
25
4
30
4
45
4
35
5
45
3
NUMBER OF
FT.
/HR.
BURNERS
3
3
4
4
5
4
MAX.
55
60
55
55
60
75
65
75
TEMP. RISE ºF AT
4
FULL INPUT
MIN.
MAX.
30
60
25
55
30
60
35
65
45
75