York CZH Installation Manual

York CZH Installation Manual

16/18 seer r-410a outdoor split-system air conditioner

Advertisement

INSTALLATION MANUAL
R-410A
OUTDOOR SPLIT-SYSTEM
AIR CONDITIONING
MODELS: 18 SEER - CZH / AC8B / AL8B SERIES
MODELS: 16 SEER - CZF / AC6B / AL6B SERIES
2 TO 5 TONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Installation with Required Clearances . . . . . . . . . . . . . . 3
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Communications Harness Connection . . . . . . . . . . . . . . . . . . . 6
Air Handler or Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
(with AC control) - PSC Air Handler . . . . . . . . . . . . . . . . . . . . . . . 8
(with AC control) - VS Air Handler . . . . . . . . . . . . . . . . . . . . . . . 9
(with AC control) - Modulating Furnace . . . . . . . . . . . . . . . . . . . 10
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . 18
TEST Input Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operational Mode Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Status Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for the highest sales volume evaporator plus 15 feet of
field supplied lines.
Matching indoor coils require a thermal expansion valve. The refriger-
ant charge may need to be changed for some system combinations,
elevation differences, or total line lengths. See tabular data sheet pro-
vided in unit literature packet for charge requirements. Refer to Applica-
tion Data covering "General Piping Recommendations and Refrigerant
Line Length" (Part Number 247077).

TABLE OF CONTENTS

SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . 17
AC CONTROL BOARD FUNCTIONALITY . . . . . . . . . . . . . 18
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
LIST OF FIGURES
Two Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . 11
Two Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . 12
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . 14
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single Stage Wiring Diagram (2 - 4 Ton) . . . . . . . . . . . . . . . . 22
Single Stage Wiring Diagram (5 Ton) . . . . . . . . . . . . . . . . . . . . 23
Two Stage Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
LIST OF TABLES
Status Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operational Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Sensor or Switch Fault Codes . . . . . . . . . . . . . . . . . . . . . . . 20
Wiring Related Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . 20
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
®
835965-UIM-C-0814

Advertisement

Table of Contents
loading

Summary of Contents for York CZH

  • Page 1: Table Of Contents

    R-410A OUTDOOR SPLIT-SYSTEM ® AIR CONDITIONING MODELS: 18 SEER - CZH / AC8B / AL8B SERIES MODELS: 16 SEER - CZF / AC6B / AL6B SERIES 2 TO 5 TONS TABLE OF CONTENTS GENERAL ........1 SYSTEM CHARGE .
  • Page 2: Unit Installation

    835965-UIM-C-0814 5. For 16 SEER models only, the unit should not be operated at out- door temperatures below 65° F without an approved low ambient operation accessory kit installed. Improper installation may create a condition where the operation of 6. The maximum allowable line length for this product is 75 feet. the product could cause personal injury or property damage.
  • Page 3: Typical Installation With Required Clearances

    835965-UIM-C-0814 THERMOSTAT 60” OVERHEAD NEC CLASS 1 CLEARANCE WIRING TO INDOOR NEC CLASS 2 BLOWER WEATHERPROOF WIRING DISCONNECT SWITCH TO COIL 24” SERVICE ACCESS CLEARANCE SEAL OPENINGS WITH PERMAGUM OR EQUIVALENT 10” COIL NOTE: ALL OUTDOOR WIRING CLEARANCE AREA A0202-001 MUST BE WEATHERPROOF FIGURE 1: Typical Installation with Required Clearances GROUND INSTALLATION...
  • Page 4: Tubing Hanger

    835965-UIM-C-0814 PIPING CONNECTIONS TO INDOOR COI L TO OUTDOOR UNIT LI QUID LINE INSULA TED VAPOR LINE CONDU IT This system uses R-410A refrigerant which operates at higher pres- sures than R-22. No other refrigerant may be used in this system. Gauge sets, hoses, refrigerant containers, and recovery systems must be designed to handle R-410A.
  • Page 5: Evacuation

    835965-UIM-C-0814 3. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to 8. Protect the vapor valve with a wet rag and braze the vapor line con- wrap the valve body with a wet rag. Allow the nitrogen to continue nection to the outdoor unit.
  • Page 6: Communications Harness Connection

    835965-UIM-C-0814 FIELD CONNECTIONS POWER WIRING NOTICE 1. Install the proper size weatherproof disconnect switch outdoors and within sight of the unit. To eliminate erratic operation, seal the hole in the wall at the ther- mostat with permagum or equivalent to prevent air drafts affecting 2.
  • Page 7: Communicating Ac With Communicating

    835965-UIM-C-0814 DEHUMIDIFICATION CONTROL Communicating Air Conditioner Non-Communicating Touch Screen A dehumidification control accessory 2HU06700124 may be used with Indoor Communicating Indoor Unit Communicating variable speed air handlers or furnaces in high humidity areas. This Interface Control Control Control control works with the variable speed indoor unit to provide cooling at a reduced air flow, lowering evaporator temperature and increasing latent capacity.
  • Page 8: Thermostat Wiring - Single Stage Air Conditioner (With Ac Control) - Psc Air Handler

    835965-UIM-C-0814 For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section. Single Stage Air Conditioner (with AC control) – PSC Air Handler ID MODELS THERMOSTAT SINGLE STAGE S1-THSU21P1b AIR HANDLER CONDITIONER...
  • Page 9: Thermostat Wiring - Single Stage Air Conditioner (With Ac Control) - Vs Air Handler

    835965-UIM-C-0814 Single Stage Air Conditioner (with AC control) - V/S Air Handler ID MODELS THERMOSTAT VARIABLE SINGLE STAGE S1-THSU21P1b SPEED AIR HANDLER CONDITIONER VARIABLE SPEED SINGLE STAGE AIR HANDLER AIR CONDITIONER CONTROL 24 – Volt Common 24 – Volt Common 24 –...
  • Page 10: Thermostat Wiring - Single Stage Air Conditioner (With Ac Control) - Modulating Furnace

    835965-UIM-C-0814 Single Stage Air Conditioner (with AC control) – Modulating Furnace ID MODELS (Y,L,C)*9C T*9C T*(8,L)C THERMOSTAT (Y,L,C)*(8,L)C SINGLE STAGE MODULATING S1-THSU21P1b FURNACE CONDITIONER MODULATING SINGLE STAGE FURNACE CONTROL AIR CONDITIONER 24 – Volt Common 24 – Volt Common 24 – Volt Common First Stage First Stage Compressor First Stage Compressor...
  • Page 11: Thermostat Chart - Two Stage Ac - Two Stage Variable Speed Furnaces

    835965-UIM-C-0814 AC 24A Two Stage Air Conditioner – Two Stage Variable Speed Furnace ID MODELS TM8V TM9V THERMOSTAT THERMOSTAT TWO STAGE TWO STAGE *DN22U00124 *PP32U70124 VARIABLE SPEED FURNACE CONDITIONER TWO STAGE VARIABLE SPEED FURNACE CONTROL 24 – Volt Common 24 – Volt Common 24 –...
  • Page 12: Thermostat Chart - Two Stage Ac - Two Stage Variable Speed Furnaces

    835965-UIM-C-0814 AC 24B Two Stage Air Conditioner – Two Stage Variable Speed Furnace ID MODELS TM8V TM9V THERMOSTAT THERMOSTAT TWO STAGE TWO STAGE *DN22C00124 *DP22U70124 VARIABLE SPEED FURNACE CONDITIONER TWO STAGE VARIABLE SPEED FURNACE CONTROL 24 – Volt Common 24 – Volt Common 24 –...
  • Page 13: Thermostat Chart - Two Stage Ac

    835965-UIM-C-0814 AC 26A Two Stage Air Conditioner – Variable Speed Modulating Furnace ID MODELS LPLC YP9C LP9C YPLC CPLC CP9C TPLC TP9C THERMOSTAT THERMOSTAT VARIABLE SPEED TWO STAGE *DN22U00124 *PP32U70124 MODULATING FURNACE CONDITIONER VARIABLE SPEED MODULATING FURNACE CONTROL 24 – Volt Common 24 –...
  • Page 14: Thermostat Chart - Two Stage Ac

    835965-UIM-C-0814 AC 26B Two Stage Air Conditioner – Variable Speed Modulating Furnace ID MODELS YPLC YP9C LPLC LP9C CPLC CP9C TPLC TP9C THERMOSTAT THERMOSTAT VARIABLE SPEED TWO STAGE *DN22C00124 *DP22U70124 MODULATING FURNACE CONDITIONER VARIABLE SPEED MODULATING FURNACE CONTROL 24 – Volt Common 24 –...
  • Page 15: Thermostat Chart - Two Stage Ac - Variable Speed Furnaces

    835965-UIM-C-0814 AC 31A Two Stage Air Conditioner – Variable Speed Air Handler ID MODELS THERMOSTAT THERMOSTAT TWO STAGE VARIABLE SPEED *DN22U00124 *PP32U70124 AIR HANDLER CONDITIONER VARIABLE SPEED AIR HANDLER CONTROL 24 – Volt Common 24 – Volt Common 24 – Volt Common 24 –...
  • Page 16: Thermostat Chart - Two Stage Ac - Variable Speed Furnaces

    835965-UIM-C-0814 AC 31B Two Stage Air Conditioner – Variable Speed Air Handler ID MODELS THERMOSTAT THERMOSTAT TWO STAGE VARIABLE SPEED *DN22C00124 *DP22U70124 AIR HANDLER CONDITIONER VARIABLE SPEED AIR HANDLER CONTROL 24 – Volt Common 24 – Volt Common 24 – Volt Common 24 –...
  • Page 17: R-410A Saturation Properties

    835965-UIM-C-0814 SECTION VI: SYSTEM CHARGE Subcooling Charging Method This condensing unit must only be used with the matching thermostatic expansion valve kit listed in the Tabular Data Sheet. This unit must be charged during cooling single stage operation (Y1), second-stage Refrigerant charging should only be carried out by a qualified air (Y1 &...
  • Page 18: Test Input Functionality

    835965-UIM-C-0814 5. The indoor coil and drain pan should be inspected and cleaned reg- NOTICE ularly to prevent odors and assure proper drainage. On 5 Ton unit the outdoor fan motor is a permanent magnet DC brushless type. The motor requires a separate Electronic Control to operate.
  • Page 19: Operational Mode Display

    835965-UIM-C-0814 TABLE 2: TEST Input Functionality Duration of Control Behavior with no system Control behavior with system connection (seconds) master signals present master signals present < 2 No response No response Bypass ASCD (Reduce timer to zero immediately). Display compressor type TS, Ultratech, or If Y1 (thermostat or communication) is present and the single stage compressor, Ignore LPS high-pressure switch is closed, contactors will be energized.
  • Page 20: Operational Fault Codes

    835965-UIM-C-0814 FAULT CODE DISPLAY LOCKOUT MODES The control will display any fault code that is currently active using the Soft Lockout LED’s. The control will display the fault code, pause two seconds, and The control will cause a soft lockout during the following conditions. display the fault again.
  • Page 21: Cooling Operation

    835965-UIM-C-0814 COOLING OPERATION When the compressor is started following a high-pressure switch fault, the control will start a six-hour timer based on accumulated compressor First-Stage Cooling Operation run time. If the control senses another opening of the high-pressure During first-stage cooling operation, the control will receive a thermostat switch before the timer expires, it will cause a soft lockout condition.
  • Page 22: Wiring Diagram

    835965-UIM-C-0814 SECTION IX: WIRING DIAGRAM BLU/PNK BLU/PNK BRN/PNK BRN/PNK FIGURE 18: Single Stage Wiring Diagram (2 - 4 Ton) Johnson Controls Unitary Products...
  • Page 23: Single Stage Wiring Diagram (5 Ton)

    835965-UIM-C-0814 FIGURE 19: Single Stage Wiring Diagram (5 Ton) Johnson Controls Unitary Products...
  • Page 24 835965-UIM-C-0814 FIGURE 20: Two Stage Wiring Diagram Johnson Controls Unitary Products...
  • Page 25: Start Up Sheet

    835965-UIM-C-0814 SECTION X: START UP SHEET Air Conditioning and Heating Start-Up Sheet Print Form Reset Form Proper start-up is critical to customer comfort and equipment longevity Start-Up Date Technician Performing Start-Up Installing Contractor Name Owner Information Name Address City State or Province Zip or Postal Code Equipment Data Upflow...
  • Page 26 Explain the importance of regular filter replacement and equipment maintenance Comments Section Subject to change without notice. Published in U.S.A. 835965-UIM-C-0814 Copyright © 2014 by Johnson Controls, Inc. All rights reserved. Supersedes: 835965-UIM-B-0813 York International Corp. 5005 York Drive Norman, OK 73069...

Table of Contents