230 Vac Auxiliary Supply; 24 Vdc Auxiliary Supply; Signal Connections; Cu230P-2 Control Unit - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

4.7.1

230 VAC auxiliary supply

The fuse must not exceed 16 A.
The connection is protected inside the cabinet with a 3 A fuse.
Connecting
● On terminal block -X40, remove the jumpers between terminals 1 and 2 as well as 3 and 4.
● Connect the external 230 V AC supply to terminals 2 (L1) and 4 (N).
Maximum connectable cross-section: 4 mm²
4.7.2

24 VDC auxiliary supply

The fuse must not exceed 10 A.
The power requirement is 2 A.
Connecting
Connect the external 24 VDC supply to terminals 1 (P 24 V) and 2 (M
Maximum connectable cross-section: 1.5 mm²
4.8

Signal connections

4.8.1

CU230P-2 Control Unit

One of the following CU230P-2 Control Units that handles the communication and open-
loop/closed-loop control functions is provided as closed-loop module:
Control Unit
Fieldbus interface
Digital inputs
Analog inputs
Digital outputs
Analog outputs
Motor temperature sensor
connection
Option short codes
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
CU230P-2 PN
CU230P-2 DP
PROFINET IO
PROFIBUS DP
6
6
4
4
3
3
2
2
1
1
K96
K97
Electrical installation
4.8 Signal connections
) of terminal block –X9.
ext
CU230P-2 HVAC
CU230P-2 CAN
RS485 (USS,
CANopen
Modbus RTU,
BACnet MS/TP, P1)
6
6
4
4
3
3
2
2
1
1
K98
K99
71