Auxiliary Power Supply, 230 Vac (Option K74) - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Electrical installation
4.9 Other connections
4.9.1

Auxiliary power supply, 230 VAC (option K74)

Description
The auxiliary power supply provides the auxiliary voltages required for external control
circuits of the cabinet unit on the plant side.
Adapting the auxiliary power supply (-T10)
A transformer (-T10) is installed to produce the auxiliary voltages of the cabinet unit. The
location of the transformer is indicated in the layout diagrams supplied.
When delivered, the transformer is always set to the highest level. Where necessary,
jumpers must be used to convert to the existing line voltage.
The tables below show the appropriate transformer setting for the control power supply
based on the existing line voltage.
Table 4- 34
Once the jumpers have been set, the secondary voltage should be 230 VAC.
NOTICE
Material damage due to voltage set too high
If the terminals are not connected to the actual line voltage, this can damage the device in
the case of the voltage being set too high.
• Connect the terminals according to the actual line voltage.
104
Line voltage assignments for the internal power supply
Line voltage
380 V
400 V
415 V
440 V
460 V
480 V
Jumper at the transformer position (-T10)
31 - 38
32 – 38
31 – 37
32 – 37
32 – 36
33 – 36
Operating Instructions, 12/2014, A5E32923362A
Inverter cabinet units

Advertisement

Table of Contents
loading