Connection For External Auxiliary Equipment (Option L19) - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Commissioning
During commissioning, the dv/dt filter plus Voltage Peak Limiter must be logged on using
STARTER or the IOP operator panel (p0230 = 2). This automatically limits the pulse
frequency to permissible values.
NOTICE
Damage to the dv/dt filter due to lack of activation after restoring to factory settings
Not activating the dv/dt filter plus Voltage Peak Limiter after restoring to factory settings can
lead to damage to the dv/dt filter.
• Activate the dv/dt filter plus Voltage Peak Limiter after restoring to factory settings with
4.9.5

Connection for external auxiliary equipment (option L19)

Description
This option includes an outgoing feeder fused with max. 10 A for external auxiliary
equipment (for example, separately driven motor fan). The voltage is tapped at the drive
input upstream of the input contactor/circuit breaker and, therefore, has the same level as
the supply voltage. The outgoing circuit can be switched within the drive or externally.
Connecting
Table 4- 36
Terminal
NO: Normally-open contact
1)
Max. connectable cross-section: 4 mm²
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
the parameter p0230 = 2.
Terminal block X155 - Connection for external auxiliary equipment
Designation
1
L1
2
L2
3
L3
11
Contactor control
12
13
NO: Checkback
motor circuit breaker
14
15
NO: Contactor feed-
back signal
16
PE
PE
1)
Electrical installation
4.9 Other connections
Technical data
3 AC 380 ... 480 V
230 V AC
230 V AC / 0.5 A
24 V DC / 2 A
240 V AC / 6 A
PE
109