8.1.5 Restore to normal operation after "Load Off"

NOTE !
Make sure the UPS to be status of the activation of "Load Off":
Switches Q1 and Q4 are closed (Pos. I),
Switch Q2 is open (Pos. O);
Battery fuse F8 – F9 are inserted;
LED Alarm is lit (load is not protected by UPS);
LED Operation is Off.
View of the synoptic diagram after pressing
the key "Load Off".
1.
Reset "Load Off".
Restore the command "Load Off" by
entering the screen:
COMMANDS / RESET LOAD OFF
The load is now powered from inverter.
LED Alarm is Off and the LED Operation must be
lit.
The synoptic diagram must display the status
"LOAD SUPPLIED BY INVERTER".
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Home\Commands
COMMANDS
RESET LOAD OFF
REQUEST LOAD OFF
Operating Manual SitePro 10-15-20-30-40 kVA / S8
Page 71/99